| 2020-10-20 07:08:41 | PLAN REVIEW GENERATOR - FUEL GAS |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | CITY RECORDS INDICATE AN EXISTING GAS SERVICE AT THIS |
| | RESIDENCE. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | |
| | 1) GAS ISOMETRIC DRAWING: |
| | 1A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM |
| | INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST |
| | REMOTE OUTLET. THE BTUH LOAD OF EACH EXISTING APPLIANCE |
| | AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON |
| | THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. (NOT |
| | ADDRESSED) (PROVIDE TOTAL LOAD OF EXISTING APPLIANCES - |
| | W/H, DRYER, RANGE AND FUTURE BBQ GRILL) |
| | |
| | NOTE: YOU MAY PROVIDE THE EXISTING LOAD AS ONE |
| | CALCULATION ON THE GAS RISER |
| | |
| | 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| | FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH |
| | LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & |
| | G2413.4.3. (NOT ADDRESSED) |
| | |
| | 1B) CORRECTED |
| | 1C) CORRECTED |
| | |
| | |
| | |