| Plan Review Notes For Permit 20060999 |
| Permit Number |
20060999 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-22 10:54:28 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ITEMS THAT ARE HI-LIGHTED ON PAGE 11 OF THE FLAT | | | ROOF PRODUCT APPROVAL ARE NOT CORRECT. FBC 107 & FBC-R | | | CHAPTER 3. | | | | | | A)THE DEFAULT EXPOSURE CATEGORY IS C. IN ORDER TO USE | | | EXPOURE B, AN ENGINEER WOULD NEED TO PROVIDE AN | | | EVALUATION. | | | B) THE BUILDING IS ENCLOSED NOT OPEN. AN OPEN STRUCTURE | | | DOES NOT HAVE ANY WALLS. | | | C) THE ROOF HEIGHT IS THE AVERAGE HEIGHT OF THE SLOPED | | | ROOF OF THE BUILDING OR THE HEIGHT OF THE FLAT ROOF IF | | | IT IS HIGHER THAN THE SLOPED ROOF. A BUILDING WILL ONLY | | | HAVE ONE MEAN ROOF HEIGHT. |
|