| Plan Review Notes For Permit 20060970 |
| Permit Number |
20060970 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-14 08:40:17 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | NO ADDED VALUE FOR THE ADDITIONAL WORK SHOWN ON PLANS. | | | | | | NO LOW VOLTAGE SHOWN ON PLANS SEPARATE PERMIT IS | | | REQUIRED FOR LOW VOLTAGE WORK. (ONE TV OUTLET SHOWN) | | | | | | PANTRY REQUIRES OUTLETS PER 210.52(C)(1) | | | | | | 210.52 (C) COUNTERTOPS. IN KITCHENS, PANTRIES, | | | BREAKFAST ROOMS, DINING ROOMS, AND SIMILAR AREAS OF | | | DWELLING UNITS, RECEPTAC LE OUTLETS FOR COUNTERTOP | | | SPACES SHALL BE INSTALLED IN ACCORDANCE WITH | | | 210.52(C)(1) THROUGH (C)(5). (1) WALL COUNTERTOP | | | SPACES. A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH | | | WALL COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER. | | | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT | | | ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.) | | | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT | | | SPACE. | | | |
|