Plan Review Notes
Plan Review Notes For Permit 20060969
Permit Number 20060969
Review Stop M
Sequence Number 1
Notes
Date Text
2020-07-08 11:47:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20060969
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MP-1 NOTE (1) INDICATES THE MECHANICAL
 CONTRACTOR TO INSTALL A COMPLETE OPERATING SYSTEM. THE
 DRAWINGS DO NOT SHOW THIS SYSTEM, IT ONLY SHOWS DUCT
 WORK FOR NEW MASTER CLOSET AND MASTER BATH AREA. WHERE
 IS THE DUCTWORK FOR THE REST OF THE 2ND STORY? IF THIS
 IS A NEW SYSTEM PLEASE PROVIDE ENERGY CALCULATIONS
 ALONG WITH THE MANUAL J CALCULATIONS FOR THE NEW
 SYSTEM. FBC EC R4.3.7.1
  
 2) PLEASE PROVIDE SPECS FOR THE BATH EXHAUST FAN AND
 SHOW IT ON THE DRAWING, ALONG WITH THE EXHAUST
 TERMINATION LOCATION. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved