| 2020-07-08 11:47:27 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20060969 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET MP-1 NOTE (1) INDICATES THE MECHANICAL |
| | CONTRACTOR TO INSTALL A COMPLETE OPERATING SYSTEM. THE |
| | DRAWINGS DO NOT SHOW THIS SYSTEM, IT ONLY SHOWS DUCT |
| | WORK FOR NEW MASTER CLOSET AND MASTER BATH AREA. WHERE |
| | IS THE DUCTWORK FOR THE REST OF THE 2ND STORY? IF THIS |
| | IS A NEW SYSTEM PLEASE PROVIDE ENERGY CALCULATIONS |
| | ALONG WITH THE MANUAL J CALCULATIONS FOR THE NEW |
| | SYSTEM. FBC EC R4.3.7.1 |
| | |
| | 2) PLEASE PROVIDE SPECS FOR THE BATH EXHAUST FAN AND |
| | SHOW IT ON THE DRAWING, ALONG WITH THE EXHAUST |
| | TERMINATION LOCATION. FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |