| 2020-07-02 16:14:43 | 1ST REVIEW FBC-2017 RES. PLUMBING |
| | PERMIT- 20060943 |
| | 7/2/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: PLEASE CLARIFY THE SCOPE OF WORK FOR |
| | PLUMBING. THE DRAWING APPEARS TO SHOW AN ENTIRE NEW DWV |
| | SYSTEM TO BE INSTALLED, INCLUDING ALL NEW UNDERSLAB |
| | SANITARY DRAIN PIPING- SECTION 107.2.1 WPB. |
| | |
| | 2) P1- SANITARY RISER: A) PROVIDE THE SIZE OF THE |
| | WASHING MACHINE FIXTURE DRAIN, AND VENT- SECTION 406.2 |
| | FBC P. B) PROVIDE THE SIZE OF THE AAV AT THE DOUBLE |
| | BOWL KITCHEN SINK- SECTION P3114.6 FBC RES. |
| | |
| | 3) P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW WATER |
| | HEATER INDICATING MAKE, MODEL, GALLON SIZE AND |
| | EFFICIENCY RATING- TABLE C404.2 FBC EC. PROVIDE A WATER |
| | HEATER PAN AND PAN DRAIN, AND SHOW THE TERMINATION |
| | LOCATION OF THE PAN DRAIN PIPE- SECTIONS P2801.6.1, |
| | P2801.6.2, AND P2801.6.2 FBC RES. |
| | |
| | 4) P1: PROVIDE THE DIMENSIONS OF THE NEW SHOWERS, AND |
| | THE WIDTH OF THE NEW SHOWER DOOR- SECTION P2708.1 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |