| 2020-06-25 14:41:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 1 - THE KEY NOTES OF THE NEW FLOOR PLAN |
| | INDICATES A # 2 AT THE NEW WALL AREA AS GYPSUM WLL WITH |
| | 1/2" DRYWALL; HOWEVER, NOTE # 5 FOR THE EXISTING WALL |
| | INDICATES 1 HOUR RATED. |
| | |
| | THE NEW WALL IS REQUIRED TO BE 1 HOUR FIRE RATED, THE |
| | SAME AS EXISTING. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEET A 1 - NEW DOORS # 5 & 6 ARE REQUIRED TO BE |
| | FIRE RATED AS THEY AS WITHIN A REQUIRED FIRE RATED |
| | WALL. THE DOOR SCHEDULE DOES NOT INDICATE ANY FIRE |
| | RATING FOR THESE DOORS. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) SHEET A 1 - THERE IS AN INDICATION OF A NEW STORAGE |
| | ROOM WITH A NEW SEPARATION WALL. |
| | |
| | THE SEPARATION WALL IS REQUIRED TO BE RATED BE THE |
| | HAZARD CLASSICATION OF THE TYPE OF STORAGE. MOST |
| | STORAGE AREAS ARE CLASSIFIED AS ORDINARY HAZARD AND A 2 |
| | HOUR SEPARATION IS REQUIRED; 1 HOUR IF THE BUILDING IS |
| | SPRINKLERED. |
| | |
| | PER NFPA 101 CH 6 |
| | |
| | 6.2 HAZARD OF CONTENTS. |
| | 6.2.1 GENERAL. |
| | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF |
| | CONTENTS SHALL |
| | BE THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE, |
| | THE DANGER OF |
| | SMOKE OR GASES GENERATED, AND THE DANGER OF EXPLOSION |
| | OR OTHER |
| | OCCURRENCE POTENTIALLY ENDANGERING THE LIVES AND SAFETY |
| | OF THE |
| | OCCUPANTS OF THE BUILDING OR STRUCTURE. |
| | 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE |
| | REGISTERED |
| | DESIGN PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE |
| | AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL |
| | ON THE BASIS |
| | OF THE CHARACTER OF THE CONTENTS AND THE PROCESSES OR |
| | OPERATIONS |
| | CONDUCTED IN THE BUILDING OR STRUCTURE. |
| | 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| | DEGREES OF |
| | HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A |
| | BUILDING OR STRUCTURE, |
| | THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION, |
| | UNLESS |
| | HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED |
| | IN SECTION |
| | 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH |
| | 43. |
| | 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS. |
| | 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY |
| | BUILDING OR |
| | STRUCTURE SHALL BE CLASSIFIED AS LOW, ORDINARY, OR HIGH |
| | IN |
| | ACCORDANCE WITH 6.2.2.2, 6.2.2.3, AND 6.2.2.4. |
| | 6.2.2.2* LOW HAZARD CONTENTS. LOW HAZARD CONTENTS SHALL |
| | BE |
| | CLASSIFIED AS THOSE OF SUCH LOW COMBUSTIBILITY THAT NO |
| | SELFPROPAGATING |
| | FIRE THEREIN CAN OCCUR. |
| | 6.2.2.3* ORDINARY HAZARD CONTENTS. ORDINARY HAZARD |
| | CONTENTS SHALL |
| | BE CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH |
| | MODERATE RAPIDITY OR |
| | TO GIVE OFF A CONSIDERABLE VOLUME OF SMOKE. |
| | 6.2.2.4* HIGH HAZARD CONTENTS. HIGH HAZARD CONTENTS |
| | SHALL BE |
| | CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH |
| | EXTREME RAPIDITY OR FROM |
| | WHICH EXPLOSIONS ARE LIKELY. (FOR MEANS OF EGRESS |
| | REQUIREMENTS, SEE |
| | SECTION 7. 11.) |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | |
| | 4) SHEET A 1 - THERE ARE NO INDICATION OF ANY EXISTING |
| | LIFE SAFETY SYSTEMS. |
| | |
| | PLEASE PROVIDE A NOTE INDICATING IF THERE IS A FIRE |
| | SRINKLER OR FIRE ALARM SYSTEM. |
| | |
| | ANY WORK ON THESE SYSTEMS SHALL BE DONE UNDER SEPARATE |
| | PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |