| Plan Review Notes For Permit 20060902 |
| Permit Number |
20060902 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-27 12:16:13 | POOL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 - FBC | | | R4501.6 | | | 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE | | | ENGINEER. | | | 2) PLEASE SHOW THE CONCRETE STEEL REINFORCING SIZE AND | | | LAP REQUIREMENTS. | | | 3) PLEASE UPDATE OR CORRECT THE CODE SECTIONS | | | REFERENCED IN THE GENERAL NOTES ON THE DRAWINGS | | | (BARRIER REQUIREMENTS FBC 4501.17) | | | | | | FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ENGINEER OR ARCHITECT DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP | | | BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS | | | ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE | | | REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN | | | REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING | | | [email protected] AND ASKING FOR THE FORM. (AT THIS TIME DROP | | | BOX ITEMS MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO | | | PLAN REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING | | | DEPT.) |
|