| 2020-06-25 06:57:26 | THE SUBMITTED SIGNED & SEALED LETTER FROM MICHAEL | | | COSTELLO, PE IS UNACCEPTABLE. SECTION 704.2 OF THE | | | FLORIDA BUILDING CODE-PLUMBING CLEARLY STATES THAT THE | | | SIZE OF THE DRAINAGE PIPING SHALL NOT BE REDUCED IN | | | SIZE IN THE DIRECTION OF THE FLOW AND THAT IS EXACTLY | | | THE ISSUE WITH THIS INSTALLATION. AN 8-INCH PIPE IS | | | DISCHARGING INTO A 6-INCH PIPE. IT IS IRRELEVANT | | | WHETHER THE SMALLER SIZE PIPE SIZE CAN HANDLE THE | | | FIXTURE DEMAND, THE CODE IS CLEAR. THEREFORE THE | | | CURRENT INSTALLATION IS NON-COMPLIANT AND MUST BE | | | CHANGED IN ORDER TO MEET THE CODE REQUIREMENT AND BE | | | APPROVED.ALSO, REFER TO FBC-PLUMBING SEC.706.2 | | | (OBSTRUCTIONS). | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH BUILDING DIVISION | | | 401 CLEMATIS ST. | | | P.O. BOX 3147 | | | WEST PALM BEACH, FL.33402 | | | [email protected] | | | P: 561-805-6692 | | | F: 561-805-6676 | | | |
|