2020-07-07 19:34:17ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. GROUNDING ELECTRODE CONDUCTOR IS SHOWN CONNECTING TO
 THE BUSBAR OF THE (EXISTING) MAIN BREAKER PANEL, THEN
 TO THE NEW SERVICE DISCONNECTING MEANS. THEN CONNECTS
 ON THE LOAD SIDE OF THE NEW SERVICE DISCONNECT/ MICRO
 GRID INTERCONNECT DEVICE. GROUNDING ELECTRODE CONDUCTOR
 MUST CONNECT TO SAME BUS AS GROUNDED CONDUCTOR IN
 SERVICE DISCONNECTING MEANS. 250.24A1
  
 2. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL
 SERVICE CONFIGURATION. NEC 220.16A1&2, 220.12, 220.14
 FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1
  
 3. TESLA SERVICE DISCONNECT SHOWS 200AMP MAIN BREAKER,
 BUT THEN NOTE SAYS 150AMP MAIN BREAKER. PLEASE CLARIFY?
 FBC 107.2.1
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  