| 2020-06-24 16:45:12 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION |
| | STATES "REPLACE THE EXISTING SLIDING GLASS DOORS (2)", |
| | WHILE ENGINEERING PLANS SUBMITTED ARE FOR THE |
| | REPLACEMENT OF THE SLIDING GLASS DOORS AND WINDOWS. |
| | REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE |
| | VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL |
| | FEES. OR PROVIDE COPIES OF ALL SIGNED CONTRACTS FOR |
| | BUILDING OFFICIAL REVIEW/APPROVAL. |
| | |
| | 3- PROVIDE COMPLETE SLIDING GLASS FLORIDA PRODUCT |
| | APPROVAL. PRODUCT APPROVAL SUBMITTED IS MISSING THE |
| | FLORIDA PRODUCT APPROVAL COVER PAGE. THIS PAGE IS |
| | REQUIRED BECAUSE IT SHOWS THE CURRENT CODE VERSION AND |
| | THE PRODUCT APPROVAL STATUS. CHAPTER 553 F.S. AND FAC |
| | 61G20-3.001. |
| | NOTE: THIS APPLIES TO SINGLE HUNG WINDOWS AND WINDOW |
| | MULLIONS ALSO IF THEY ARE GOING TO BE REPLACED ALSO. |
| | |
| | 4- SLIDING GLASS DOORS PRODUCT APPROVAL DRAWINGS |
| | SUBMITTED ARE MISSING SHEET 1 OF 7. PROVIDE COMPLETE |
| | PRODUCT APPROVAL DRAWINGS. FAC 61G20-3.001. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 5- IF INSTALLING THE WINDOWS, THEN PROVIDE PRODUCT |
| | APPROVAL AS REQUIRED BY FAC 61G20-3.001 FOR WINDOW |
| | MULLIONS AS SHOWN ON PLANS. AND CLEARLY SPECIFY MULLION |
| | SIZE TO BE USED TO VERIFY COMPLIANCE WITH THE |
| | CALCULATED DESIGN PRESSURES. SEC. 1609.1 FBC-BUILDING. |
| | |
| | |