| 2020-07-10 15:30:31 | ROOFING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT |
| | APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED |
| | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR |
| | ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE |
| | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-52.5) |
| | - SEE NOTE LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL. |
| | SIGNED AND SEALED DRAWINGS OR DOCUMENTS WILL NEED TO BE |
| | DIGITALLY SIGNED AND SEALED TO BE USED IN ELECTRONIC |
| | PLAN REVIEW. SHOW THE WIND DESIGN DATA USED PER 2017 |
| | FBC AND ASCE 7-10 - WIND SPEED - EXPOSURE - RISK |
| | CATEGORY - ETC. |
| | |
| | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| | ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG |
| | WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON |
| | FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| | AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS |
| | MAY TAKE 2 TO 3 WEEKS TO PROCESS - DUE TO LIMITED STAFF |
| | INSIDE THE BUILDING DEPT.) |
| | |