2020-08-11 16:56:2108/11/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. YOU CANNOT
 SUBMIT AN OLD DRAWING OF A PAST PERMIT REVIEW DOCUMENT
 WITH A STAMPED OF AN OLD PERMIT ON AND REDLINE IT.
 PLEASE REDRAW WITH CLARITY AND ANSWER COMMENT AS BEST
 AS YOU CAN, YOU CAN USE ALL THE INFORMATION ON THE OLD
 PERMIT REVIEW. THERE IS A DRAWING UPLOADED BUT SOME OF
 THESE COMMENTS YOU MAY HAVE DONE ALREADY ON IT.
  
 A. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP
 CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 C. CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF THE
 PIPE OF THE NEW SYSTEM PER THE 2017 FBC RES. SECS.
 G2413.4.1, G2413.4.2.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
  
 E. LIST THE BTU LOAD OF EACH APPLIANCE OF THE OLD AND
 ADD THE TOTAL BTU LOADS ON THE NEW SYSTEM WITH A TOTAL
 PER THE 2017 FBC RES. SEC. G2413.
  
 F. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
  
 G. PLACE A NOTE ON PLANS LISTING THE SIZING TABLES FROM
 GAS CODES OR ANOTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS SYSTEM PER THE 2017 FBC RES. SEC.
 G2413.3.
  
 H. PLEASE SHOW AND LABEL UNIONS IN FRONT OF REGULATOR
 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2.
  
 I. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 J. SHOW DRIP LEG AND LABEL ON EQUIPMENT INSTALLED PER
 THE 2017 FBC RES. SEC. G2419.2.
  
 K. PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES PER THE 2017 FBC RES. SEC. G2413.4.1,
 G2413.4.2 & G2413.4.3.
  
 L. PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR PER THE 2017 FBC RES. SEC.
 G2421.1.
  
 M. PROVIDE THE BTU'S LOAD OF THE GENERATOR NOT KW PER
 THE 2017 FBC RES. SEC. G2413.2.
  
 N. ON THE EXISTING GAS SHOW THE SIZE TO THE MAIN BRANCH
 AND PUT NOT ON IT SAYING EXISTING GAS AND TO A TOTAL OF
 ALL FIXTURE. YOU DON'T NEED TO SHOW PIPES, FITTING AND
 OTHER APERTURES, JUST MAKE SURE THE SCHEDULE IS NOTED
 ON A LIST AS ASKED ON ITEM E.
  
 2. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR GAS EQUIPMENT FROM
 GENERAC, THERE IS A VERSION IN 2020 AS THE NEW SPEC
 CALL OUT THE GENERATOR AT 309 BTU'S TO VERIFY
 COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE FBC RES. SEC. G2421.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  