| Plan Review Notes For Permit 20060789 |
| Permit Number |
20060789 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-20 15:51:12 | PLAN REVIEW ? GENERATOR - ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER | | | SWITCH. ? ATS | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2) ELCTRICAL RISER DIAGRAHM. NEC 215.5; WPB FBC 107.2.1 | | | 2A) INCLUDE MAIN DISCONNECT AND ANY SUB PANELS. | | | 2B) RISER SHOWS ONLY ONE #14 CONTROL WIRE. IS THIS | | | CORRECT? | | | 2C) SHOW GROUNDING ELECTROCDE AT SERVICE. | | | | | | 3) LOAD CALCULATIONS. IDENTIFY PANEL EACH LOAD CALC. | | | REPRESENTS. | | | PROVIDE LOAD CALCULATION FOR SERVICE,OR SERVICES, | | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE | | | E3602.2 | | | | | | | | | |
|