2020-07-20 15:51:12PLAN REVIEW ? GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ? ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2) ELCTRICAL RISER DIAGRAHM. NEC 215.5; WPB FBC 107.2.1
 2A) INCLUDE MAIN DISCONNECT AND ANY SUB PANELS.
 2B) RISER SHOWS ONLY ONE #14 CONTROL WIRE. IS THIS
 CORRECT?
 2C) SHOW GROUNDING ELECTROCDE AT SERVICE.
  
 3) LOAD CALCULATIONS. IDENTIFY PANEL EACH LOAD CALC.
 REPRESENTS.
 PROVIDE LOAD CALCULATION FOR SERVICE,OR SERVICES,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
  
  
  