| Plan Review Notes For Permit 20060787 |
| Permit Number |
20060787 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-18 17:05:47 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | COMMENTS ARE FOR THE NEW GARAGE BUILDING ONLY. | | | | | | PAGE E.2.1 SIDE ENTRANCE TO THE GARAGE NEEDS A LIGHTING | | | OUTLET/SWITCH 210.70(A)(2)(B) | | | | | | (B) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED | | | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL | | | SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO | | | PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR | | | ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. A VEHICLE | | | DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN OUTDOOR | | | ENTRANCE OR EXIT | | | | | | PAGE E.1.1 DISCONNECT AT NEW GARAGE NEEDS A GROUNDING | | | ELECTRODE SYSTEM 250.32(A) | | | | | | (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S) | | | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A | | | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM | | | INSTALLED |
|