| 2020-07-27 12:35:38 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20060770 |
| | 7/27/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P-102 & P-103: PLEASE VERIFY THE DISTANCE |
| | FROM THE SHOWER TRAP TO THE VENT IN BATH-2 DOES NOT |
| | EXCEED 8 FT. PER TABLE P3105.1 FBC RES. |
| | 2) P-102 & P-103: SHOW HOW THE NEW SHOWER IN BATH #3 IS |
| | BEING VENTED- SECTION P3101.2.1 FBC RES. |
| | 3) PROVIDE A SHOWER PAN DETAIL- SECTIONS P2709.1 & |
| | P2709.2 FBC RES. |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| | HEATER- SECTION P2801.3 FBC RES. |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SHOWER |
| | AND BATHTUB VALVES- SECTIONS P2708.4 & P2713.3 FBC RES. |
| | 6) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED |
| | FOR THE GAS PIPING INSTALLATION. THE GAS ISOMETRIC ON |
| | P-103 WILL NOT BE REVIEWED AT THIS TIME- SECTION |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |