2020-06-26 14:31:51RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- FLAT ROOF NOA 18-0919.12 SUBMITTED: SELECTED
 ASSEMBLY ON PAGE 53 OF 67 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. CLEARLY IDENTIFY WHICH
 FASTENING OPTION IS GOING TO BE USED AND PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. 1609.1 FBC-BUILDING.
 NOTE: FASTENING OPTIONS WITH GENERAL LIMITATION #9 CAN
 NOT BE USED. SEE GENERAL LIMITATION #9 ON LAST PAGE OF
 NOA.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,