| 2021-08-17 15:59:47 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20060761 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SHOW HOW THE VENTILATION FOR ALL SPACES OF |
| | THIS TENANT SPACE WILL MEET FBC M 401.3 (VENTILATION |
| | SHALL BE PROVIDED DURING THE PERIODS THAT THE ROOM OR |
| | SPACE IS OCCUPIED.) |
| | |
| | 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS BASED ON THE NATURAL VENTILATION OF THE |
| | CHANGE OF USE OF THE SPACES. FBC EC C403.2.1 |
| | |
| | 3) PLEASE ADDRESS ALL OF THE COMMENTS FROM THE 1ST |
| | CYCLE MECHANICAL REVIEW LISTED BELOW. |
| | |
| | |
| | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20060761 |
| | |
| | |
| | |
| | 2) PLEASE PROVIDE COMPLETE DRAWINGS OF THE EXISTING |
| | MECHANICAL SYSTEM AND INCLUDE ANY NEW CHANGES. THIS |
| | DRAWING MUST SHOW THE RATED WALLS USED AS SEPARATION |
| | BETWEEN THE NEW OCCUPANCIES WITH DAMPERS IF ANY DUCT |
| | WORK IS PENETRATING THESE RATED WALLS. FBC FS 107.2.1 |
| | |
| | 3) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THIS NEW |
| | PROJECT, FOR ALL AREAS. THE NATURAL VENTILATION |
| | CALCULATIONS IN THIS PACKAGE WOULD NOT WORK AS THERE |
| | SHOULD BE A RATED WALL BETWEEN THE F-2 AND B |
| | OCCUPANCIES. FBC M 403 |
| | |
| | 4) PLEASE PROVIDE QUANTITIES OF INGREDIENTS STORED AT |
| | THIS FACILITY. FBC FS 107.2.1 |
| | |
| | 5) PLEASE SHOW THE EXHAUST FOR THE MASH AREA. FBC FS |
| | 107.2.1 |
| | |
| | 6) PLEASE PROVIDE A VENTING DETAIL FOR THE CO2 TO AN |
| | APPROVED TERMINATION LOCATION. FBC FS 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |