| 2020-07-07 14:44:30 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20060761 |
| | 7/7/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE PLUMBING FIXTURE CALCULATIONS. PROVIDE A |
| | SCHEDULE ON THE PLAN SHOWING THE REQUIRED AND PROVIDED |
| | NUMBER OF FIXTURES PER TABLE 403.3 FBC P. PLEASE NOTE |
| | THAT DRINKING FOUNTAINS AND SERVICE SINKS ARE REQUIRED |
| | FOR F AND A OCCUPANCIES. AN EMERGENCY SHOWER AND EYE |
| | WASH STATION MAY BE REQUIRED FOR THE F OCCUPANCY |
| | DEPENDING UPON DEPARTMENT OF HEALTH, DEPARTMENT OF |
| | AGRICULTURE, OSHA, OR OTHER GOVERNING AGENCY |
| | REQUIREMENTS. PLEASE CONTACT THOSE AGENCIES FOR FURTHER |
| | INFORMATION. |
| | |
| | 2) SHEET A.100: PLEASE LABEL THE TOILET ROOMS AS EITHER |
| | MALE OR FEMALE- SEE SECTIONS 403.2 AND 403.2.1 FBC P. |
| | THE PLAN INDICATES THE TOILET ROOMS ARE EXISTING. |
| | PLEASE PROVIDE ENLARGED DRAWINGS AND DETAILS TO VERIFY |
| | COMPLIANCE WITH SECTION 1006.1 FBC EX, AND SECTION |
| | 601.1 FBC ACC. |
| | |
| | 3) A.100: THE PLAN INDICATES ACCESS TO ONE OF THE TWO |
| | TOILET ROOMS IS THROUGH A STORAGE AND BREWERY AREA |
| | WHICH IS NOT ALLOWED PER SECTION 403.3.1 FBC P. |
| | |
| | 4) A.100: THE PLAN SHOWS NEW SINKS IN WHAT APPEARS TO |
| | BE A BAR AREA, HOWEVER PLUMBING PLANS WERE NOT PROVIDED |
| | FOR THE PROPOSED PROJECT. PLEASE SUBMIT PLUMBING PLANS |
| | SHOWING THE LOCATIONS OF ALL NEW OR RELOCATED FIXTURES, |
| | FLOOR DRAINS, TRENCH DRAINS, INDIRECT WASTE RECEPTORS, |
| | ETC. PROVIDE SANITARY AND WATER RISER ISOMETRIC |
| | DRAWINGS, AND FLAT LINE PIPING PLANS SHOWING THE POINTS |
| | OF CONNECTIONS TO THE EXISTING DWV AND WATER |
| | DISTRIBUTION SYSTEMS- SECTIONS 107.2.1 AND 107.3.5.1.1 |
| | WPB. THE WATER RISER SHALL PROVIDE SYMBOLS TO INDICATE |
| | THE LOCATIONS OF REQUIRED BACKFLOW PREVENTERS, WATER |
| | HAMMER ARRESTORS, TRAP PRIMERS, SHUT OFF VALVES, AND |
| | ALL PIPING CONNECTIONS TO PROCESS OR BREWERY EQUIPMENT |
| | AND TANKS (IF APPLICABLE). |
| | |
| | 5) PROVIDE PLUMBING FIXTURE AND DEVICE SCHEDULES |
| | INDICATING MAKES AND MODELS AND LISTING AND LABELING |
| | INFORMATION- SECTION 303 FBC P. |
| | |
| | 6) REFER TO SECTION 1003.3.1 FBC P: A GREASE |
| | INTERCEPTOR WILL BE REQUIRED TO RECEIVE THE DRAINAGE |
| | FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN WASTE |
| | LOCATED IN THE BREWERY AND PROCESSING AREAS. SHOW ON |
| | THE PLANS THE DRAINAGE SYSTEM FOR THE TANKS AND KETTLES |
| | AND OTHER PROCESS EQUIPMENT. |
| | |
| | 7) SHEET 8: REFER TO TABLE 608.1 AND SUBMIT SPECS FOR |
| | THE WATER SUPPLY HOSE BIB AND BACKFLOW PREVENTER, AND |
| | THE FDA HOSE AND CARBON FILTER- SECTION 107.2.1 WPB. |
| | |
| | 8) SHEET 6: SHOW THE WATER FEED CONNECTION TO THE COLD |
| | WATER TANK. CLARIFY IF THE TANK WILL BE MANUALLY FILLED |
| | USING THE HOSE OR IF IT WILL BE HARD-PIPED- SEE SECTION |
| | 608.1 FBC P. |
| | |
| | 9) ACCESSIBILITY: PLEASE BE ADVISED THAT ALL NEW |
| | PLUMBING FIXTURES FOR PUBLIC USE SHALL BE ACCESSIBLE- |
| | SECTION 201.1 FBC ACC. THE SUBMITTED PLANS ARE NOT |
| | SHOWING ANY NEW PUBLIC USE FIXTURES, HOWEVER ALL |
| | REVISED PLANS INDICATING NEW FIXTURE INSTALLATIONS, |
| | INCLUDING THE REQUIRED DRINKING FOUNTAINS, SHALL |
| | INCLUDE INSTALLATION DRAWINGS AND DETAILS IN COMPLIANCE |
| | WITH SECTION 601.1 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |