Plan Review Notes
Plan Review Notes For Permit 20060739
Permit Number 20060739
Review Stop B
Sequence Number 2
Notes
Date Text
2020-07-09 07:55:12PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 THE PROPOSED FLOORING UNDERLAYMENT (PROFLEX 90 MSC)
 DOES NOT APPEAR TO MEET THE TEST REQUIREMENTS AS NOTED
 ON THE LAST PLAN REVIEW (ASTM E 84, ASTM E90, & ASTM
 E492) FOR A 6" THICK SLAB.
 PLEASE RESUBMIT A FLOORING UNDERLAYMENT COMPLETE WITH
 THE APPROVED TEST RESULTS FOR THIS APPLICATION.