Plan Review Notes
Plan Review Notes For Permit 20060739
Permit Number 20060739
Review Stop B
Sequence Number 1
Notes
Date Text
2020-06-24 15:21:252017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060739
 ADD: 701 S. OLIVE AVE. SUITE # 1501
 CONT: FLORIDA STATE RESTORATION SERVICES
 TEL: 954-426-9494
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 24TH/ 2020
 ACTION: DENIED
  
 1) THE 3 ARCHITECTURAL SHEETS APPEAR TO BE PAPER PLANS
 THAT WERE SCANNED AND UPLOADED TO BEING ELECTRONIC
 VERSIONS. THE ARCHITECT MARINA N. LLORENE DOES NOT
 APPEAR TO HAVE SIGNED THE PLANS DIGITALLY.
 ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING
 PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER
 DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY
 THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE
 CHARGE.
 (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT
 BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE.
 (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS
 CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE
 DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER
 AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES
 THE MANUAL SEALING PROCEDURE SET OUT IN RULE
 61G1-16.003, F.A.C.
 (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A
 DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL
 ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
 (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN
 AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST
 DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD
 PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012,
 WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE
 BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE
 S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE
 INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP
 S/FIPS180-4/FIPS-180-4.PDF.
  
 2) IN THE SUPPORTING DOCUMENT FILE THERE WAS A DATA
 SHEET FOR PROFLEX 90 MSC, NO TEST REPORTS. FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2D) THE CITY HAS A FILE IN OUR COMPUTER FOR FLOOR
 UNDERLAYMENT?S. WE HAVE NO INFORMATION ON PROFLEX 90
 MSC. WE DO HAVE THE TEST REPORTS (ALL 3) FOR PROFLEX
 SUPERSIM 90 APPLIED TO A 6 INCH CONCRETE SLAB FOR
 MARBLE & TILE.
 ASTM E-90 STC 52 DB
 ASTM E-492 IIC 50 DB
 FLAME SPREAD ASTM E 84
 IF THIS PRODUCT IS WHAT YOU WOULD LIKE TO USE NOTE SO
 ON THE PLANS, NO TEST REPORTS ARE REQUIRED.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  