Plan Review Notes
Plan Review Notes For Permit 20060735
Permit Number 20060735
Review Stop B
Sequence Number 2
Notes
Date Text
2020-10-07 16:57:28PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. ONLY ONE SET IS
 REQUIRED TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED
 DOCUMENTS.
  
 2) THE INFORMATION SUBMITTED FOR THE SINGLE HUNG
 WINDOWS DOES NOT HAVE AN FL# AND DOES NOT APPEAR TO BE
 THE PRODUCT APPROVAL. SUBMIT THE COMPLETE PRODUCT
 APPROVAL WITH THE FL COVERSHEET. FBC 107.3.4
  
 3) THE DOCUMENTS SUBMITTED FOR THE SINGLE HUNG WINDOWS
 HAVE A DESIGN PRESSURE OF + OR - 50 PSF. THIS IS NOT
 ADEQUATE FOR WINDOWS C & D IN THE CONVERTED GARAGE OR
 WINDOW L IN THE TWO STORY HOUSE. THEY HAVE PRESSURES
 THAT EXCEED -50 PSF.
  
 4) SUBMIT THE PRODUCT APPROVALS FOR THE DOORS AND THE
 STRUCTURAL MULLIONS. FBC 107.3.4
  
 5) THE DOCUMENTS SUBMITTED FOR THE SINGLE HUNG WINDOWS
 ARE FOR NON-IMPACT RATED WINDOWS. IMPACT PROTECTION IS
 REQUIRED FOR THE GLAZED OPENINGS PER FBC-R301.2.1.2
 PROTECTION OF OPENINGS. SUBMIT A KEY PLAN, INSTALLATION
 SCHEDULE AND PRODUCT APPROVALS FOR THE STORM PANELS.
 FBC 107
  
 6) THE ENERGY FORMS ARE REQUIRED TO BE SIGNED BY THE
 PREPARER AND THE OWNER/AGENT. FBC ENERGY CONSERVATION
 SECTION 405.4
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
  
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
  
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM. THIS HELP TO SHORTEN THE REVIEW TIME.
  
  
  
  
  
  
  
  
  