| 2020-10-07 16:57:28 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. ONLY ONE SET IS |
| | REQUIRED TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED |
| | DOCUMENTS. |
| | |
| | 2) THE INFORMATION SUBMITTED FOR THE SINGLE HUNG |
| | WINDOWS DOES NOT HAVE AN FL# AND DOES NOT APPEAR TO BE |
| | THE PRODUCT APPROVAL. SUBMIT THE COMPLETE PRODUCT |
| | APPROVAL WITH THE FL COVERSHEET. FBC 107.3.4 |
| | |
| | 3) THE DOCUMENTS SUBMITTED FOR THE SINGLE HUNG WINDOWS |
| | HAVE A DESIGN PRESSURE OF + OR - 50 PSF. THIS IS NOT |
| | ADEQUATE FOR WINDOWS C & D IN THE CONVERTED GARAGE OR |
| | WINDOW L IN THE TWO STORY HOUSE. THEY HAVE PRESSURES |
| | THAT EXCEED -50 PSF. |
| | |
| | 4) SUBMIT THE PRODUCT APPROVALS FOR THE DOORS AND THE |
| | STRUCTURAL MULLIONS. FBC 107.3.4 |
| | |
| | 5) THE DOCUMENTS SUBMITTED FOR THE SINGLE HUNG WINDOWS |
| | ARE FOR NON-IMPACT RATED WINDOWS. IMPACT PROTECTION IS |
| | REQUIRED FOR THE GLAZED OPENINGS PER FBC-R301.2.1.2 |
| | PROTECTION OF OPENINGS. SUBMIT A KEY PLAN, INSTALLATION |
| | SCHEDULE AND PRODUCT APPROVALS FOR THE STORM PANELS. |
| | FBC 107 |
| | |
| | 6) THE ENERGY FORMS ARE REQUIRED TO BE SIGNED BY THE |
| | PREPARER AND THE OWNER/AGENT. FBC ENERGY CONSERVATION |
| | SECTION 405.4 |
| | |
| | PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY |
| | COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR |
| | INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL |
| | CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 |
| | & FBC 117. |
| | |
| | FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A |
| | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| | PURPOSES UNTIL APPROVED. |
| | |
| | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER |
| | ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL |
| | FORM. THIS HELP TO SHORTEN THE REVIEW TIME. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |