2020-07-15 14:50:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20060710 6300 GARDEN AVE
  
 2ND REVIEW
  
 GAS COMMENTS:
  
 1. SECOND REQUEST: PLEASE SHOW WHERE THIS BBQ IS
 LOCATED AND SHOW WALLS AND CEILING DETAIL. FBC 107.2.1.
 TO BE CLEAR, A HOUSE PLAN SHOWING THE LOCATION OF THE
 APPLIANCES INCLUSIVE OF THOSE OUTDOORS WITH THE
 LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS
 IN RELATION TO THE APPLIANCES IS REQUIRED. THE LOCATION
 OF THE APPLIANCES SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. PLEASE NOTE THAT
 OPEN PERMIT 20031407 FOR POOL INDICATES THAT THE POOL
 EQUIPMENT WHICH WOULD INCLUDE THE POOL HEATER IS
 LOCATED ON A WALL NEAR TWO (2) WINDOWS (SEE CLOSED
 PERMIT 16010471).
 2. SECOND REQUEST: SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES
 TO BE CLEAR, THIS SHALL INCLUDE GALVANIZED PIPING
 AND/OR CSST AT THE APPLIANCE. IF CSST IS USED, THE
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL SHALL
 BE SUBMITTED AND ALL MANUFACTURER?S RECOMMENDATION
 INCLUDING BUT NOT LIMITED TO PROTECTION OF EXPOSED
 PIPING SHALL BE ADHERED TO PER FBC FG 404.2.
 3. SECOND REQUEST: SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR THE BBQ GRILL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 NEW COMMENTS
 1. RE: ISOMETRIC (RISER DIAGRAM)
 A. TOTAL DEMAND HAS BEEN INCREASED BY 450 MBTU. PER WPB
 FBC 107.2.1, PROVIDE SIZING OF PIPING FROM METER TO
 CONNECTION OF NEW LINE. PIPING SHALL SUPPORT TOTAL 649
 MBTU AT LESS THAN 2PSI FOR A LONGEST LENGTH DISTANCE
 FOR THE SYSTEM WHICH IS 60 FEET AND SHALL BE SIZED PER
 TABLE 402.4(2). PLEASE NOTE THAT CLOSED PERMIT 16051054
 INDICATES THE EXISTING PIPING IS 1 INCH WHICH IS
 INADEQUATE.
 B. THE LONGEST LENGTH DISTANCE FOR THE SYSTEM, 90 FEET
 AS NOTED ON ISOMETRIC PIPING TO RANGE APPEARS TO BE
 INCORRECT. ACCORDING TO CLOSED PERMIT 16051054, THE
 ACTUAL DISTANCE FROM THE METER TO EXISTING RANGE IS 55
 FEET SO THE CORRECT LONGEST LENGTH OF 60 FEET IS
 APPLICABLE AS DESCRIBED IN SUBMITTED TABLE 402.4(21).
 THE PE BRANCH TO THE POOL HEATER IS UNDERSIZED AT 3/4
 INCH AND SHALL BE 1-1/4 INCH TO SUPPORT 400 MBTU.
 C. PER WPB FBC 107.2.1, INDICATE THE TRANSITION FITTING
 OR RISER COMPLYING WITH FBC FG 417.1 AND 417.2 FROM PE
 PIPING TO ABOVE GROUND SCHEDULE 40 GALVANIZED PIPING;
 INDICATE THE GALVANIZED PIPING.
 D. PER WPB FBC 107.2.1, PROVIDE NOTE SHOWING COMPLIANCE
 WITH FBC FG 417.3 STATING YELLOW INSULATED COPPER
 TRACER WIRE OR OTHER APPROVED CONDUCTOR SHALL BE
 INSTALLED ADJACENT TO UNDERGROUND NONMETALLIC PIPING.
 ACCESS SHALL BE PROVIDED TO THE TRACER WIRE OR THE
 TRACER WIRE SHALL TERMINATE ABOVE GROUND AT EACH END OF
 THE NONMETALLIC PIPING. THE TRACER WIRE SIZE SHALL BE
 NOT LESS THAN 18 AWG AND THE INSULATION TYPE SHALL BE
 SUITABLE FOR DIRECT BURIAL.
 E. PER WPB FBC 107.2.1, IDENTIFY SHUT OFF VALVES FOR
 APPLIANCES; A SEDIMENT TRAP IS REQUIRED COMPLYING WITH
 FBC FG 408.4.
 F. AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE GAS/PLUMBING
 PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR
 THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THAT TRADE.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  