| 2020-06-29 11:15:20 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20060703 |
| | ADD: 1701 S. FLAGLER DR. # 506 |
| | CONT: AOA CONSTRUCTION |
| | TEL: 561-660-3504 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 29TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) WIND CHART FROM ENGINEERING EXPRESS: |
| | 1A) THE WIND CHART FORM ENGINEERING EXPRESS COULD NOT |
| | VERIFY THE DIGITAL SIGNATURE. |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES), |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | DIGITALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 1B) THE SUBMITTED WIND CHART FROM ENGINEERING EXPRESS |
| | IS ONLY GOOD FOR BUILDINGS < (LESS THAN 60 FEET). THIS |
| | HIGHRISE IS APPROXIMATELY 230 FEET ABOVE GRADE. NOTE TO |
| | CONTRACTOR NEGATIVE PRESSURES FOR COMPONENTS AND |
| | CLADDING ARE ALWAYS TAKEN FROM THE MRH (MEAN ROOF |
| | HEIGHT). 2017 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS |
| | FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR |
| | THE BUILDING. |
| | 1C) ) THE SUBMITTED WIND CHART FROM ENGINEERING EXPRESS |
| | NEITHER ARE THE WALL ZONES IDENTIFIED ON THE SIDE |
| | ELEVATIONS AND ON THE PRESSURE CHARTS OPENING SIZES AND |
| | PRESSURES ARE NOT IDENTIFIED. |
| | 2) THE SUBMITTED PRODUCT APPROVALS DIDN?T HAVE THE |
| | FOLLOWING INFORMATION IDENTIFIED. PLEASE IDENTIFY ON |
| | THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | 3) PLEASE NOTE THE FOLLOWING 3 FILES WERE LOADED WRONG, |
| | FAILED TO OPEN: |
| | 3.1) 1XFRVUM1.RJI |
| | 3.2) JOOOE3PQP.WZH |
| | 3.3) RBV4W5R5.PZN |
| | YOU MAY HAVE TO CONTACT THE PERMIT LIBRARIANS: |
| | LAURA MARCHANT 561-805-6658 |
| | OR CAROLINA CARVAJAL 561-805-6690 |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| 2020-06-29 10:02:16 | SEE BUILDING PLAN REVIEW |