| 2020-09-18 12:39:28 | 3RD REVIEW FBC-2017 RES. |
| | PERMIT- 20060671 |
| | 9/16/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | 1) THE WATER HEATER DETAIL APPEARS TO HAVE BEEN CUT-OFF |
| | AND IS MISSING THE LOCATION OF THE REQUIRED EXPANSION |
| | TANK- P2903.4.2 FBC RES. THE DETAIL ALSO SHOWS THE HEAT |
| | TRAP ON THE HW LINE RUNNING THROUGH THE ADJACENT WALL |
| | INSTEAD IN A LOCATION AS CLOSE TO THE WATER HEATER AS |
| | POSSIBLE- SECTION R403.5.5 FBC EC. IT APPEARS A PAN |
| | WILL NOT BE INSTALLED UNDER THE WATER HEATER SO PLEASE |
| | INDICATE THE RELIEF VALVE DISCHARGE PIPE WILL DISCHARGE |
| | A MINIMUM OF 1? FROM THE BUILDING PER SECTION R318.5 |
| | FBC RES. |
| | |
| | 2) ADVISORY: THE REVISED ENERGY COMPLIANCE FORM |
| | R405-2017 INDICATES THE EFFICIENCY RATING OF THE GAS |
| | WATER HEATER AT 0.59 ON PAGE 1 AND PAGE 4. THE OVERALL |
| | REPORT HAS PASSED CODE WITH THE DATA INSERTED, HOWEVER |
| | PLEASE NOTE THAT PER TABLE C404.2 FBC EC THE MINIMUM |
| | EFFICIENCY RATING FOR A 40-GALLON GAS-FIRED STORAGE |
| | TANK WATER HEATER IS 80% E. |
| | |
| | 3) SHEET EP1: 3RD REQUEST TO SHOW THE 2? WASHING |
| | MACHINE DRAIN CONNECTING TO A 3? VERTICAL STACK- |
| | SECTION 406.2 FBC P. |
| | |
| | 4) EP1: PLEASE RELOCATE THE LAVATORY FIXTURE DRAIN |
| | CONNECTION SHOWN AT THE BASE OF THE WASHING MACHINE |
| | STACK TO THE ADJACENT LAVATORY BRANCH DRAIN. THIS IS A |
| | DOUBLE BOWL SINK AND THE FIXTURE DRAINS WILL TYPICALLY |
| | SHARE THE COMMON VENT- SECTION P307.1 FBC P. |
| | |
| | 5) EP1: IN ACCORDANCE WITH THE RESPONSE NARRATIVE |
| | PLEASE PLACE A LIST OF DEFERRED SUBMITTALS ON THE PLAN |
| | TO INCLUDE THE WATER HEATER, SHOWER, BATHTUB VALVE, |
| | SHOWER VALVE, AND THE IN-WALL TANK WATER CLOSET. |
| | ADVISORY: PLEASE NOTE THE WATER HEATER GALLON SIZE IS |
| | DETERMINED BY PEAK DEMAND CALCULATIONS PROVIDED BY THE |
| | MANUFACTURER (NOT PROVIDED) AND IN ACCORDANCE WITH |
| | TABLE P2903.1 FBC RES. |
| | |
| | 6) EP1: 2ND REQUEST TO PLACE BOLD NOTES ON THE PLAN |
| | INDICATING SEPARATE PERMITS ARE REQUIRED FOR THE GAS |
| | PIPING AND BACKFLOW PREVENTER. PLEASE NOTE COMPLETE |
| | PLANS, AND EQUIPMENT AND APPLIANCE SPECIFICATIONS ARE |
| | REQUIRED FOR INSTALLATION OF THE GAS PIPING SYSTEM |
| | INCLUDING A GAS RISER DRAWING, COMBUSTION AND MAKEUP |
| | AIR CALCULATIONS, AND VENTING PLANS- SECTION 105.1 AND |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |