| 2020-09-16 09:27:31 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20060671 |
| | 9/16/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | PLEASE NOTE THAT FIVE OF THE SUPPORTING DOCUMENTS DID |
| | NOT UPLOAD PROPERLY AND CANNOT BE OPENED AND REVIEWED |
| | IN THE PROGRAM. EACH DOC HAS AN ERROR MESSAGE INCLUDING |
| | THE ENERGY COMPLIANCE SUBMITTAL AND THE COMMENT |
| | RESPONSE NARRATIVE. THOSE DOCS ARE ESSENTIAL TO |
| | REVIEWING AND APPROVING THE PLUMBING PLANS. |
| | |
| | 1) SHEET EP1: 2ND REQUEST TO SHOW THE 2 IN. WASHING |
| | MACHINE DRAIN CONNECTING TO A 3 IN. VERTICAL STACK- |
| | SECTION 406.2 FBC P. |
| | |
| | 2) EP1: INDICATE THE REQUIRED MINIMUM 1/4 IN. AND |
| | MAXIMUM 1/2 IN. PER FT. SLOPE TO DRAIN IN THE SHOWER |
| | PAN DETAIL- SECTION P2709.1 FBC RES. |
| | |
| | 3) EP1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE ON |
| | THE PLAN AND SUBMIT THE MANUFACTURER'S SPECIFICATIONS |
| | FOR THE UNIT AS PREVIOUSLY REQUESTED. PLEASE NOTE THAT |
| | A STORAGE TYPE WATER HEATER WILL REQUIRE INSTALLATION |
| | OF A DEVICE TO CONTROL THERMAL EXPANSION WHICH MOST |
| | TYPICALLY IS A THERMAL EXPANSION TANK- SECTION P2903.4 |
| | FBC RES. PLEASE NOTE THE EFFICIENCY RATING OF THE WATER |
| | HEATER SHALL BE INCLUDED IN THE ENERGY COMPLIANCE |
| | SUBMITTAL WHICH CANNOT BE REVIEWED AT THE PRESENT TIME- |
| | TABLE C404.2 FBC EC. |
| | |
| | 4) EP1: PLEASE PROVIDE A NOTE OR DETAIL SHOWING THE |
| | DISCHARGE PIPING SERVING THE WATER HEATER |
| | PRESSURE-RELIEF VALVE, TEMPERATURE RELIEF VALVE, OR |
| | COMBINATION VALVE IS IN COMPLIANCE WITH SECTION |
| | P2904.6.1 ITEMS 1-14. IF DISCHARGING INTO A PAN, A |
| | DRAIN LINE FROM THE PAN SHALL TERMINATE A MINIMUM A |
| | MINIMUM OF 1FT. FROM THE BUILDING- SECTION R318.5 FBC |
| | RES. |
| | |
| | 5) EP1, WATER RISER: WATER HAMMER ARRESTOR MISSING AT |
| | DISHWASHER SUPPLY LINE- SECTION P2717.1 FBC RES. PLEASE |
| | NOTE TYPICALLY A DISHWASHER GETS ONLY A COLD WATER |
| | SUPPLY FEED - HOT AND COLD SUPPLY LINES ARE SHOWN. A) |
| | 2ND REQUEST TO SHOW THE SUPPLY LINE TO THE REFRIGERATOR |
| | ICE MAKER (IF TO BE INSTALLED) AND THE REQUIRED WATER |
| | HAMMER ARRESTOR AND BACKFLOW DEVICE- SECTIONS P2717.1, |
| | P2902.1 P2903.5 FBC RES. |
| | |
| | 6) 2ND REQUEST TO SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR: |
| | A) WATER HEATER- SECTION P2801.3 FBC RES. |
| | B) SHOWER AND BATHTUB VALVES- SECTIONS P2708.4 & |
| | P2713.3. |
| | C) IN-WALL TANK TOILET- SECTION P2712.1. |
| | PLEASE NOTE THE SHOWER VALVE, BATHTUB VALVE, AND |
| | IN-WALL TANK TOILET SUBMITTALS MAY BE DEFERRED. PLEASE |
| | PLACE A NOTE ON THE PLAN IF APPLICABLE. |
| | |
| | 6) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED |
| | FOR THE GAS PIPING INSTALLATIONS TO THE WATER HEATER, |
| | DRYER, AND RANGE- SECTION 107.2.1 WPB. PLACE A NOTE ON |
| | THE PLAN ACCORDINGLY. |
| | |
| | 7) EP1: THE SIGNATURE OF THE LICENSED CONTRACTOR OR |
| | QUALIFIER WHO PREPARED THE PLUMBING DRAWINGS SHALL BE |
| | ON THE PLAN PER SECTION 107.1 WPB AND AND FLORIDA |
| | STATUTES 471.003(2)(H) & 471.025. IF THE DESIGNER IS A |
| | FL. LICENSED ENGINEER OR ARCHITECT, THE PLAN SHALL BEAR |
| | HIS/HER ELECTRONIC SEAL AND SIGNATURE- FL. STATUTES |
| | 471.025, 481.221 AND SECTIONS 61G1-16.005, 61G15-23.005 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 8) ADVISORY: PLEASE NOTE THAT A FL. LICENSED PLUMBING |
| | CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| | WITH SECTION 105.1 WPB AND SEC, 90-33 WPB CODE OF |
| | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| | FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |