| 2020-07-27 15:26:21 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20060671 |
| | 7/27/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A3: SHOW THE DIMENSIONS OF THE SHOWER AND THE |
| | BATHTUB IN THE MASTER BATHROOM, AND THE DIMENSIONS OF |
| | THE SHOWER IN BATH 2- SECTION P2708.1 FBC RES. |
| | |
| | 2) SHEET EP-1: THE PLUMBING RISER IS NOT CODE |
| | COMPLIANT. |
| | A) NO VENTS ARE SHOWN FOR THE MASTER BATH SHOWER AND |
| | TUB- SECTION P3101.2.1 FBC RES. |
| | B) THE MASTER BATH FIXTURES AND POWDER ROOM FIXTURES |
| | ARE NOT BEING PROPERLY VENTED- SEE SECTIONS P3108.1 & |
| | P3108.2.1 FBC RES. IN ORDER FOR THE TOILET TANK VENT TO |
| | SERVE AS THE DRY VENT FOR THE HORIZONTAL WET VENT |
| | SERVING THE TWO BATH GROUPS, IT MUST CONNECT |
| | HORIZONTALLY TO THE HORIZONTAL WET VENT- THE DRAWING |
| | SHOWS A VERTICAL CONNECTION. ADDITIONALLY, NOT MORE |
| | THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE |
| | UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION- |
| | THE DRAWING SHOWS THREE BATH FIXTURES. |
| | C) ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL |
| | CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. THE |
| | CLOTHES WASHING MACHINE FIXTURE DRAIN- P3108.1 SHALL |
| | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. PLEASE |
| | NOTE THAT THE 2? WASHING MACHINE DRAIN SHALL CONNECT TO |
| | A 3? FIXTURE BRANCH OR VERTICAL STACK- SECTION 406.2 |
| | D) THE ISOMETRIC FOR BATH-2 SHOWS TWO FIXTURES |
| | DISCHARGING UPSTREAM OF THE DRY VENT AT THE LAVATORY- |
| | ONLY ONE FIXTURE IS ALLOWED TO DISCHARGE UPSTREAM- |
| | SECTION P3108.1. |
| | |
| | 3) PROVIDE A WATER RISER DRAWING SHOWING THE WATER |
| | DISTRIBUTION PIPING RUNS INCLUDING THE TYPES AND SIZES |
| | OF PIPING, AND SHUT OFF VALVE LOCATIONS- SECTION |
| | 107.3.5.3 WPB. PLEASE INCLUDE THE SUPPLY LINES TO THE |
| | DISHWASHER AND REFRIGERATOR ICE MAKER SHOWING THE |
| | REQUIRED BACKFLOW PREVENTERS AND WATER HAMMER |
| | ARRESTORS- SECTIONS P2717.1, P2902.1 P2903.5 FBC RES. |
| | |
| | 4) PROVIDE A SHOWER PAN DETAIL- SECTIONS P2709.1 & |
| | P2709.2 FBC RES. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR: |
| | A) WATER HEATER- SECTION P2801.3 FBC RES. |
| | B) SHOWER AND BATHTUB VALVES- SECTIONS P2708.4 & |
| | P2713.3. |
| | C) IN-WALL TANK TOILET- SECTION P2712.1. |
| | |
| | 6) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED |
| | FOR THE GAS PIPING INSTALLATIONS TO THE WATER HEATER, |
| | DRYER, AND RANGE- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |