| 2020-08-03 12:10:05 | PLAN REVIEW - BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. VALUE HAS BEEN ADJUSTED FROM $78,000 TO $223,099 PER |
| | ICC BUILDING VALUATION DATA. |
| | |
| | 2. PROVIDE SITE DRAINAGE PLAN. |
| | |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| | AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED ON A BOUNDARY LINE SURVEY. |
| | |
| | 3. PROVIDE A SOILS REPORT. |
| | |
| | FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE |
| | CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND |
| | REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE |
| | REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL |
| | INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY |
| | TESTING OR ENGINEERING CALCULATIONS, SUCH |
| | INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED |
| | DESIGN PROFESSIONAL. |
| | |
| | 4. PROVIDE THE FOLLOWING BUILDING PLANS - |
| | |
| | 4A) FOUNDATION PLAN. |
| | 4B) EXTERIOR WALL SECTIONS. |
| | 4C) ELEVATIONS PLANS. |
| | 4D) DETAIL PAGE. |
| | |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 5. DESIGNER SHALL SPECIFY CEILING AND WALL INSULATION |
| | ON PLANS. |
| | |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 6. PROVIDE AN ENERGY SUBMITTAL. |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | PROVIDE ENERGY GAUGE FORM R405 PER SECTION R405.2 FBC |
| | EC. |
| | |
| | 7. SUBMIT PRODUCT APPROVALS FOR WINDOWS AND DOORS. |
| | UPLOAD EACH PRODUCT APPROVAL TO PROJECT DOX AS ONE |
| | SUBMITTAL. PROVIDE APPROPRIATE NAME FOR EACH SUBMITTAL. |
| | |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. |
| | |
| | 8. REMOVE DOCUMENTS THAT ARE NOT RELEVANT TO THIS |
| | SUBMITTAL. |
| | |
| | 9. PROVIDE APPROPRIATE NAME FOR EACH SUBMITTAL. |
| | |
| | 10. DIGITAL SIGNATURE OF DESIGN PROFESSIONAL IS |
| | INVALID. SEE SIGNATURE REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |