| Plan Review Notes For Permit 20060641 |
| Permit Number |
20060641 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-07 13:35:29 | ADD AC CLOSET | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWINGS SHOULD SHOW THE BUILDING OCCUPANCY | | | CLASSIFICATION PER FBC CHAPTER 3 | | | 2) DRAWINGS SHOULD SHOW THE BUILDING CONSTRUCTION TYPE | | | PER FBC CHAPTER 6 | | | 3) DRAWINGS SHOULD SHOW THE FBC EXISTING BUILDING CODE | | | COMPLIANCE METHOD FBC E 301.1 GENERAL. | | | THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION | | | OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY | | | WITH ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 | | | THROUGH 301.1.3 AS SELECTED BY THE APPLICANT. |
|