| 2020-08-26 11:09:00 | SFR ADDITION AND REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC RESIDENTIAL, WPB |
| | AMENDMENTS |
| | |
| | 2ND REVIEW |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE ROOF SLOPE REQUIREMENT FOR THE LOW |
| | SLOPE ROOF FBC R905.9 (SHOW THE REQUIRED MINIMUM SLOPE) |
| | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR DOORS, ROOFING |
| | SYSTEMS ETC. |
| | 3) ALL PRODUCT APPROVALS AND SHOP DRAWINGS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD FBC WPB AMENDMENTS 107.3.4 |
| | 4) WINDOWS - FIXED AND CASEMENT AT BATH TUB AND SHOWER |
| | LOCATIONS = PRODUCT APPROVALS PROVIDED DO NOT SHOW |
| | SAFETY GLAZING TESTED - PLEASE ADD A NOTE TO THE |
| | DRAWINGS THAT SAFETY GLAZING IS REQUIRED PER FBC R308.3 |
| | AND R308.4.5 |
| | R308.3.1IMPACT TEST. |
| | WHERE REQUIRED BY OTHER SECTIONS OF THE CODE, GLAZING |
| | SHALL BE TESTED IN ACCORDANCE WITH CPSC 16 CFR 1201. |
| | GLAZING SHALL COMPLY WITH THE TEST CRITERIA FOR |
| | CATEGORY II UNLESS OTHERWISE INDICATED IN TABLE |
| | R308.3.1(1). |
| | |
| | EXCEPTION: GLAZING NOT IN DOORS OR ENCLOSURES FOR HOT |
| | TUBS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND |
| | SHOWERS SHALL BE PERMITTED TO BE TESTED IN ACCORDANCE |
| | WITH ANSI Z97.1. GLAZING SHALL COMPLY WITH THE TEST |
| | CRITERIA FOR CLASS A UNLESS INDICATED IN TABLE |
| | R308.3.1(2). |
| | |
| | 5) A PRODUCT APPROVAL HAS BEEN PROVIDED FOR SINGLE HUNG |
| | WINDOWS - THE DRAWINGS DO NOT SHOW A LOCATION FOR THE |
| | SINGLE HUNG WINDOWS. |
| | |
| | WILL ADD PRIVISO - TO BE PROVIDED BEFORE INSTALLATION. |
| | PLEASE PROVIDE THE "EPICORE" FLOOR DETAILS SIGNED AND |
| | SEALED BY AN ENGINEER OR ARCHITECT DESIGNED FOR THE |
| | REQUIRED LOADS FBC R301.1.3 |