2020-07-08 10:58:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-2 BALCONY ON SECOND FLOOR REQUIRED TO HAVE AN
 OUTLET.
 PROVIDE GFCI PROTECTED OUTLET ON 2ND FLOOR BALCONY. NEC
 210.52(E); FBC RE E3901.7
  
 PAGE E-3 SMOKE DETECTOR IN POOL HOUSE TO CLOSE TO
 BATHROOM DOOR PLEASE MOVE AT LEASDT 3' FROM DOOR. R-314
 FBC
  
 PAGE E-4 GROUNDING ELECTRODE SYSTEM REQUIRED AT MAIN
 HOUSE.
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
  