| Plan Review Notes For Permit 20060600 |
| Permit Number |
20060600 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-08 10:58:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-2 BALCONY ON SECOND FLOOR REQUIRED TO HAVE AN | | | OUTLET. | | | PROVIDE GFCI PROTECTED OUTLET ON 2ND FLOOR BALCONY. NEC | | | 210.52(E); FBC RE E3901.7 | | | | | | PAGE E-3 SMOKE DETECTOR IN POOL HOUSE TO CLOSE TO | | | BATHROOM DOOR PLEASE MOVE AT LEASDT 3' FROM DOOR. R-314 | | | FBC | | | | | | PAGE E-4 GROUNDING ELECTRODE SYSTEM REQUIRED AT MAIN | | | HOUSE. | | | A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE | | | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND | | | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF | | | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC | | | RE E3607.3 | | | |
|