| 2020-07-02 09:58:09 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT-20060558 |
| | 7/2/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A PLUMBING PLAN INCLUDING A SCOPE OF WORK |
| | OUTLINE AND LOCATIONS OF ALL FIXTURES TO BE REPLACED OR |
| | INSTALLED. INCLUDE A SANITARY ISOMETRIC AND WATER RISER |
| | FOR ALL RELOCATED, OR EXTENDED DWV OR WATER |
| | DISTRIBUTION PIPES- SECTION 107.2.1 WPB. |
| | |
| | 2) PLEASE NOTE: |
| | |
| | A) THE HORIZONTAL DISTANCE FROM THE CENTERLINE OF THE |
| | NEW SHOWER DRAIN OUTLET TO THE CENTERLINE OF THE INLET |
| | OF THE EXISTING TRAPS SHALL NOT EXCEED 30". PLEASE |
| | PLACE A NOTE ON THE PLAN INDICATING COMPLIANCE- SECTION |
| | 1002.1 FBC P. |
| | B) RELOCATING THE SHOWER DRAIN OUTLET MAY REQUIRE THE |
| | FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING |
| | STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A |
| | NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET- |
| | SECTION 107.2.1 WPB. |
| | C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION |
| | 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |