| Notes |
| Date |
Text |
| 2020-06-12 13:14:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) PROPOSED MECHANICAL SHEET - THERE IS INDICATION OF | | | THE DUCT WORK TIEING INTO THE HALLWAY DUCT WORK. | | | | | | THIS DUCT WORK APPEARS TO BE BREECHING A FIRE RATED | | | CORRIDOR WALL AND THERE IS NO FIRE DAMPER INDICATED. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|