Plan Review Notes
Plan Review Notes For Permit 20060551
Permit Number 20060551
Review Stop B
Sequence Number 2
Notes
Date Text
2020-08-03 15:06:03GENERATOR SLAB AND TIEDOWN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING LABELED (S-1) NEEDS TO BE SIGNED AND SEALED
 BY THE ENGINEER OR ARCHITECT WHO DESIGNED IT.
 2) DRAWING (S-1) SHOWS A 40' X 16' SLAB - ENGINEERING
 DOCUMENT FROM (WESLEY W. HAMILL) SHOWS A 9' X 20' SLAB
 - PLEASE CLARIFY.
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
  