| Plan Review Notes For Permit 20060551 |
| Permit Number |
20060551 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-08-03 15:06:03 | GENERATOR SLAB AND TIEDOWN | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWING LABELED (S-1) NEEDS TO BE SIGNED AND SEALED | | | BY THE ENGINEER OR ARCHITECT WHO DESIGNED IT. | | | 2) DRAWING (S-1) SHOWS A 40' X 16' SLAB - ENGINEERING | | | DOCUMENT FROM (WESLEY W. HAMILL) SHOWS A 9' X 20' SLAB | | | - PLEASE CLARIFY. | | | | | | FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | |
|