2020-06-30 11:50:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SCOPE OF WORK IN NOT CLEAR, ONE GENERATOR OR FOUR?
  
 NEED CUT SHEETS FOR THE GENERATORS SUBMITTED WITH
 PACKAGE.
  
 VALUE IS WAY LOW FOR 3- 500KW GENERATORS PLUS A 300KW,
 PLANS STILL INDICATE FUTURE GENERATORS??? (35,000)
  
 HOW IS ONE GENERATOR WIRED TO ANOTHER AND ANOTHER TO
 GET TO THE TRANSFER SWITCH? HOW DO YOU CALCULATE THE
 WIRE SIZES?