| Notes |
| Date |
Text |
| 2020-06-30 11:50:50 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | SCOPE OF WORK IN NOT CLEAR, ONE GENERATOR OR FOUR? | | | | | | NEED CUT SHEETS FOR THE GENERATORS SUBMITTED WITH | | | PACKAGE. | | | | | | VALUE IS WAY LOW FOR 3- 500KW GENERATORS PLUS A 300KW, | | | PLANS STILL INDICATE FUTURE GENERATORS??? (35,000) | | | | | | HOW IS ONE GENERATOR WIRED TO ANOTHER AND ANOTHER TO | | | GET TO THE TRANSFER SWITCH? HOW DO YOU CALCULATE THE | | | WIRE SIZES? |
|