Plan Review Notes
Plan Review Notes For Permit 20060550
Permit Number 20060550
Review Stop M
Sequence Number 1
Notes
Date Text
2020-06-24 09:58:44PLAN REVIEW - MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE: THE ADDITION COMMUNICATES WITH THE EXISTING
 CONDITIONED SPACE. MECH. PERMIT 18120755
  
 MECHANICAL PERMIT REQUIRED.
  
 1. SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE ADDITION
 PER FBC EC R101.5.1.1
  
 R101.5.1.1.1BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE CODE OFFICIAL TO DEMONSTRATE
 CODE COMPLIANCE BY THIS METHOD. ALTERNATIVELY, A
 FLORIDA RESCHECK COMPUTER PRINTOUT MAY BE SUBMITTED TO
 DEMONSTRATE COMPLIANCE BY SECTIONS R402, R403 AND R404.
  
 2017 FBC EXISTING BUILDING, CHPT. 11, ADDITIONS
  
 2017 FBC ENERGY, CHAPTER 5 (RE), EXISTING BUILDINGS,
  
 R303.10 REQUIRED HEATING.
  
 SUBMIT WINDOW PRODUCT DATA SHEETS TO VERIFY U-FACTORS
 AND SHGC VALUES- SECTION R405.
  
  
  