| Plan Review Notes For Permit 20060544 |
| Permit Number |
20060544 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-24 15:41:53 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR EXHAUST IS TO BE LOCATED 10 FEET FROM | | | ANY OPENINGS INTO THE STRUCTURE OR PER THE | | | MANUFACTURER'S SPECIFICATIONS. FBC FUEL GAS 616.1 | | | | | | 2) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE | | | ELECTRONICALLY SUBMITTED GENERATOR PAD DRAWINGS. FS 471 | | | & FAC 61G15 |
|