Plan Review Notes
Plan Review Notes For Permit 20060496
Permit Number 20060496
Review Stop B
Sequence Number 2
Notes
Date Text
2020-07-14 09:58:12WIN/DOOR/SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ACCORDION SHUTTERS = THE EDGE DISTANCE SHOWN ON THE
 "SHUTTER SCHEDULE" OF 1" IS NOT ALLOWED - PLEASE SEE
 PRODUCT APPROVAL SHEET 13 OF 20 FOR THE MINIMUM EDGE
 DISTANCE GUIDE.
 2) PANEL SHUTTERS = THE MIN. EDGE DISTANCE FOR BLOCK IS
 2" PER SHEET 4 ON THE PRODUCT APPROVAL.
 3) PLEASE REVISE THE "SHUTTER ATTACHMENT SCHEDULE"