2020-07-20 09:58:102ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20060467
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADDRESS THE 2 ITEMS BELOW FRO THE FIRST
 REVIEW:
  
 2) NOTE 4 OF 1ST REVIEW- THE AHU IN THE GARAGE MUST BE
 PROTECTED FROM IMPACT. FBC RES M1307.3.1
  
 3) NOTE 8 OF 1ST REVIEW- DUCTS IN THE GARAGE AND DUCTS
 PENETRATING THE WALLS OR CEILINGS SEPARATING THE
 DWELLING FROM THE GARAGE SHALL BE CONSTRUCTED OF A
 MINIMUM NO.26 GAGE SHEET METAL. FBC RES R302.5.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  