| Date |
Text |
| 2020-07-08 14:04:47 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20060467 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC |
| | 101.5.1.1.2 |
| | |
| | 2) PLEASE PROVIDE THE MANUAL S AND J CALCULATIONS. FBC |
| | RES M1401.3 |
| | |
| | 3) PLEASE PROVIDE SPEC SHEETS ON THE AHU. FBC FS |
| | 107.2.1 |
| | |
| | 4) PLEASE SHOW HOW YOU ARE PROTECTING THE AHU IN THIS |
| | GARAGE. FBC M 303.4 |
| | |
| | 5) PLEASE SHOW CONDENSATION LINES AND WHERE THEY DRAIN |
| | TO THE EXTERIOR. THE PLUMBING SHEET DOES NOT SHOW A |
| | DRAIN AT THE AHU. FBC RES M1411.3 |
| | |
| | 6) PLEASE SHOW THAT THE RETURN AIR IS BALANCED. FBC M |
| | 601.6 |
| | |
| | 7) PLEASE PROVIDE DRYER DUCT MATERIAL AND TOTAL LENGTH. |
| | FBC M 504.8.1, FBC M 504.8.3 |
| | |
| | 8) THE DRAWING INDICATES THAT THE AHU IS IN THE GARAGE, |
| | PLEASE SHOW THE DUCT FIRE RATING. FBC RES R3.2.5.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |