| Plan Review Notes For Permit 20060446 |
| Permit Number |
20060446 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-02 11:51:12 | IT DOES NOT APPEAR THAT ANY CHANGES OR CORRECTIONS HAVE | | | BEEN MADE NOR INDICATED ON THE RESUBMITTAL. | | | | | | THE BELOW COMMENTS ARE RE-ENTERED AS THEY WERE NOT | | | ADDRESSED. | | | | | | PLEASE ENSURE THAT THE COMMENTS ARE ADDRESSED, | | | CORRECTED AND CLOUDED ON THE PLAN SHEET OR PROVIDE A | | | DETAILED NARRATIVE DEFENDING WHY CORRECTIONS ARE NOT | | | REQUIRED, INCLUDING SPECIFIC ODE REFERNECES. | | | | | | ******************************************************* | | | ********************************* | | | | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET 1 OF 3 - THERE IS NO INDICATIONS OF | | | NOTIFICATION WITHIN THE KITCHEN AREAS. | | | | | | PLEASE REVIEW AND CORRECT OF JUSTIFY WITH SPECIFIC CODE | | | REFERENCES AND NARRATIVE EXPLANATION. | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS/CLEAR INDICATORS THAT THE | | | KITCHEN HOOD SYSTEMS ARE TIED INTO THE FIRE ALARM. | | | | | | PLEASE REVIEW AND CORRECT OF SPECIFICALLY INDICATE THE | | | REQUIRED RELAYS/CONNECTIONS | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|