| Plan Review Notes For Permit 20060446 |
| Permit Number |
20060446 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-16 10:25:13 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET 1 OF 3 - THERE IS NO INDICATIONS OF | | | NOTIFICATION WITHIN THE KITCHEN AREAS. | | | | | | PLEASE REVIEW AND CORRECT OF JUSTIFY WITH SPECIFIC CODE | | | REFERENCES AND NARRATIVE EXPLANATION. | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS/CLEAR INDICATORS THAT THE | | | KITCHEN HOOD SYSTEMS ARE TIED INTO THE FIRE ALARM. | | | | | | PLEASE REVIEW AND CORRECT OF SPECIFICALLY INDICATE THE | | | REQUIRED RELAYS/CONNECTIONS | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|