Plan Review Notes
Plan Review Notes For Permit 20060445
Permit Number 20060445
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-06-23 11:16:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE FOLLOWING COMMENTS ARE PROVIDED IN AN EFFORT TO
 REDUCE FALSE FIRE ALARMS WHILE REMIANING COMPLIANT WITH
 CODE.
  
 THESE COMMENTS ARE PROVIDED AS IT APPEARS TO SOME
 OVER-DESIGN INDICATED AS THIS ASSEMBLY OCCUAPNY IS
 PROTECTED THROUGHOUT WITH A COMPLETE FIRE SPRINKLER
 SYSTEM.
  
 1) SHEET 1 OF 3 - THERE ARE INDICATIONS OF PULL
 STATIONS AT EACH EXIT DOOR.
  
 PER NFPA 101
  
 12.3.4.2 INITIATION.
 12.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE BY
 BOTH OF THE FOLLOWING MEANS:
 (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1), UNLESS
 OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (A) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC FIRE
 DETECTION SYSTEM IN ACCORDANCE WITH 9.6.2.1(2) THAT
 PROVIDES FIRE DETECTION THROUGHOUT THE BUILDING.
 (B) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.6.2.1(3) THAT
 PROVIDES FIRE DETECTION AND PROTECTION THROUGHOUT THE
 BUILDING.
 (2) WHERE AUTOMATIC SPRINKLERS ARE PROVIDED, INITIATION
 OF THE
 FIRE ALARM SYSTEM BY SPRINKLER SYSTEM WATERFLOW, EVEN
 WHERE
 MANUAL FIRE ALARM BOXES ARE PROVIDED IN ACCORDANCE WITH
 12.3.4.2.1(1)
  
 THERE IS A FIRE SPRINKLER SYSTEM THROUGHOUT THE
 BUILDING.
  
 9.6.2 SIGNAL INITIATION.
 9.6.2.1 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE,
 ACTUATION
 OF THE FIRE ALARM SYSTEM SHALL OCCUR BY ANY OR ALL OF
 THE FOLLOWING
 MEANS OF INITIATION BUT SHALL NOT BE LIMITED TO SUCH
 MEANS:
 (1) MANUAL FIRE ALARM INITIATION
 (2) AUTOMATIC DETECTION
 (3) EXTINGUISHING SYSTEM OPERATION
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 ONLY 1 MANUAL FIRE ALARM BOX IS REQUIRED, THE ONE
 LOCATED AT THE MAIN DOUBLE DOOR EXIT.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 NARRATIVE AND CODE REFERENCES.
  
  
  
 2) SHEET 1 OF 3 - THERE ARE SMOKE DECTORS LOCATED
 THROUGHOUT THE OCCUPANCY.
  
 I DO NOT SEE THAT SMOKE DETECTION IS REQUIRED WITHIN
 THIS ASSEMBLY OCCUPANCY,
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 NARRATIVE AND CODE REFERENCES.
  
  
  
 3) SHEET 1 OF 3 - THERE ARE INDICATION OF HEAT
 DETECTORS WITHIN THE KITCHEN AREA.
  
 I DO NOT SEE THAT HEAT DETECTION IS REQUIRED WITHIN
 THIS AREA,
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 NARRATIVE AND CODE REFERENCES.
  
  
  
 4) SHEET 1 & 2 OF 3 - THERE IS A SYMBOL OF A SQUARE
 WITH AN M IN THE CENTER THAT IS NOT INCLUDED LEGEND.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) SHEET 1 OF 3 - THERE DOES NOT APPEAR TO BE A
 NOFICIATION DEVICE WITHIN THE SMALLER BATHROOM,ADA,
 WOMENS RESTROOM. IT DOES APPEAR IN THE MENS.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 6) SHEET 2 OF 3 - THERE IS AN INDICATION OF THE FACP
 LOCATED IN ELECTRICAL ROOM; HOWEVER, SHEET 1 OF 3 ONLY
 INDICATES THE POWER SUPPLY.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL