| 2020-06-23 11:16:51 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THE FOLLOWING COMMENTS ARE PROVIDED IN AN EFFORT TO |
| | REDUCE FALSE FIRE ALARMS WHILE REMIANING COMPLIANT WITH |
| | CODE. |
| | |
| | THESE COMMENTS ARE PROVIDED AS IT APPEARS TO SOME |
| | OVER-DESIGN INDICATED AS THIS ASSEMBLY OCCUAPNY IS |
| | PROTECTED THROUGHOUT WITH A COMPLETE FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 1) SHEET 1 OF 3 - THERE ARE INDICATIONS OF PULL |
| | STATIONS AT EACH EXIT DOOR. |
| | |
| | PER NFPA 101 |
| | |
| | 12.3.4.2 INITIATION. |
| | 12.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE BY |
| | BOTH OF THE FOLLOWING MEANS: |
| | (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1), UNLESS |
| | OTHERWISE |
| | PERMITTED BY ONE OF THE FOLLOWING: |
| | (A) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY |
| | WHERE |
| | INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC FIRE |
| | DETECTION SYSTEM IN ACCORDANCE WITH 9.6.2.1(2) THAT |
| | PROVIDES FIRE DETECTION THROUGHOUT THE BUILDING. |
| | (B) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY |
| | WHERE |
| | INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC |
| | SPRINKLER SYSTEM IN ACCORDANCE WITH 9.6.2.1(3) THAT |
| | PROVIDES FIRE DETECTION AND PROTECTION THROUGHOUT THE |
| | BUILDING. |
| | (2) WHERE AUTOMATIC SPRINKLERS ARE PROVIDED, INITIATION |
| | OF THE |
| | FIRE ALARM SYSTEM BY SPRINKLER SYSTEM WATERFLOW, EVEN |
| | WHERE |
| | MANUAL FIRE ALARM BOXES ARE PROVIDED IN ACCORDANCE WITH |
| | 12.3.4.2.1(1) |
| | |
| | THERE IS A FIRE SPRINKLER SYSTEM THROUGHOUT THE |
| | BUILDING. |
| | |
| | 9.6.2 SIGNAL INITIATION. |
| | 9.6.2.1 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, |
| | ACTUATION |
| | OF THE FIRE ALARM SYSTEM SHALL OCCUR BY ANY OR ALL OF |
| | THE FOLLOWING |
| | MEANS OF INITIATION BUT SHALL NOT BE LIMITED TO SUCH |
| | MEANS: |
| | (1) MANUAL FIRE ALARM INITIATION |
| | (2) AUTOMATIC DETECTION |
| | (3) EXTINGUISHING SYSTEM OPERATION |
| | |
| | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE |
| | DETECTION OR |
| | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM |
| | SYSTEM IN |
| | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN |
| | ONE MANUAL |
| | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY |
| | HAVING |
| | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE |
| | ALARM SIGNAL. |
| | |
| | ONLY 1 MANUAL FIRE ALARM BOX IS REQUIRED, THE ONE |
| | LOCATED AT THE MAIN DOUBLE DOOR EXIT. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | NARRATIVE AND CODE REFERENCES. |
| | |
| | |
| | |
| | 2) SHEET 1 OF 3 - THERE ARE SMOKE DECTORS LOCATED |
| | THROUGHOUT THE OCCUPANCY. |
| | |
| | I DO NOT SEE THAT SMOKE DETECTION IS REQUIRED WITHIN |
| | THIS ASSEMBLY OCCUPANCY, |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | NARRATIVE AND CODE REFERENCES. |
| | |
| | |
| | |
| | 3) SHEET 1 OF 3 - THERE ARE INDICATION OF HEAT |
| | DETECTORS WITHIN THE KITCHEN AREA. |
| | |
| | I DO NOT SEE THAT HEAT DETECTION IS REQUIRED WITHIN |
| | THIS AREA, |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| | NARRATIVE AND CODE REFERENCES. |
| | |
| | |
| | |
| | 4) SHEET 1 & 2 OF 3 - THERE IS A SYMBOL OF A SQUARE |
| | WITH AN M IN THE CENTER THAT IS NOT INCLUDED LEGEND. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 5) SHEET 1 OF 3 - THERE DOES NOT APPEAR TO BE A |
| | NOFICIATION DEVICE WITHIN THE SMALLER BATHROOM,ADA, |
| | WOMENS RESTROOM. IT DOES APPEAR IN THE MENS. |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | |
| | 6) SHEET 2 OF 3 - THERE IS AN INDICATION OF THE FACP |
| | LOCATED IN ELECTRICAL ROOM; HOWEVER, SHEET 1 OF 3 ONLY |
| | INDICATES THE POWER SUPPLY. |
| | |
| | PLEASE REVIEW AND CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |