| Plan Review Notes For Permit 20060420 |
| Permit Number |
20060420 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-06-10 14:27:51 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE PLAN SHEET INDICATES THE NEW FYER DIRECTLY ON | | | THE EDGE OF THE EXISTING HOOD ABOVE WITH NO OVERHANG. | | | | | | PER NFPA 96 | | | | | | 5.2 HOOD SIZE. HOODS SHALL BE SIZED AND CONFIGURED TO | | | PROVIDE | | | FOR THE CAPTURE AND REMOVAL OF GREASE-LADEN VAPORS. | | | (SEE 8.2.2.) | | | | | | 8.2.2 AIR VOLUME. | | | 8.2.2.1 EXHAUST AIR VOLUMES FOR HOODS SHALL BE OF A | | | SUFFICIENT | | | LEVEL TO PROVIDE FOR CAPTURE AND REMOVAL OF | | | GREASE-LADEN COOKING | | | VAPORS.8.2.2.2* TEST DATA, PERFORMANCE TESTS ACCEPTABLE | | | TO THE AUTHORITY | | | HAVING JURISDICTION, OR BOTH SHALL BE DISPLAYED, | | | PROVIDED ON | | | REQUEST, OR BOTH. | | | | | | A PREVIOUS HOOD PERMIT INDICATED THIS AS A UL 710, | | | WHICH REQUIRES A MINIMUM OF 6". | | | | | | PLEASE PROVIDE THE REQUIRED OVERHANG AND THAT THIS | | | INSTALL IS WITHIN THAT REQUIRERMENT. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|