| Date |
Text |
| 2020-12-17 05:16:56 | 4TH REVIEW FBC-2017 PLUMBING |
| | PERMIT-20060393 |
| | 12/17/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | 1). THIRD REQUEST: IT APPEARS THAT SOME CHANGES MAY |
| | HAVE BEEN MADE TO THE PROJECT THAT WERE NOT PERMITTED. |
| | PROVIDE AN EXISTING FLOOR PLAN. THE FLOOR LAYOUT OF THE |
| | EXISTING PLAN IN CITY RECORDS DOES NOT MATCH THE LAYOUT |
| | OF THE SUBMITTED PLAN. THE RESPONSE IN THE RESPONSE |
| | NARRATIVE OF " THE OLD PERMIT PLANS MUST BE INACCURATE" |
| | DOES NOT SOLVE THIS ISSUE. WORK THAT WAS PREVIOUSLY |
| | DONE WITHOUT PERMITS MUST BE LEGALLY PERMITTED. WPB |
| | AMEND. TO FBC SEC. 107.3..5, 105.1. |
| | 2. THE CENTERLINE OF THE WATER CLOSET SHALL BE 12 |
| | INCHES MINIMUM TO 15 INCHES MAXIMUM FROM THE SIDE WALL |
| | OR PARTITION FOR CHILDREN AGES 5-8 YEARS OLD FBC ACC |
| | 604.9 |
| | 3) PROVIDE THE REQUIRED CLEAR FLOOR SPACED FOR THE |
| | TOILET AND SINK IN THE NEW ADA TOILET ROOM. FBC ACC 604 |
| | 4) FOURTH REQUEST INDICATE THE ON THE PLAN THAT THE |
| | TEMPERED WATER TO THE BATHROOM SINKS HAVE A MAX 110 |
| | DEGREES BY AN APPROVED ASSE 1070 DEVICE COMPLYING WITH |
| | FBC P 607.1.2. |
| | 5) HOT WATER IS REQUIRED FOR THE STAFF LOUNGE SINK AND |
| | THE SERVICE SINK FOR CLEANING PURPOSES FBC P 607.1 |
| | 5) FOURTH REQUEST: A HIGH LOW DRINKING FOUNTAIN IS AN |
| | ACCESSIBILITY CODE REQUIREMENT FBC ACC 211.2 THE 2017 |
| | ACCESSIBILITY CODE REQUIRES AT LEAST A HIGH & LOW |
| | DRINKING FOUNTAIN INCOMPLIANCE WITH 2017 FBC ACC 211.2 |
| | MINIMUM NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS |
| | SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY |
| | WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN |
| | SHALL COMPLY WITH 602.7. THE WATER DISPENSER IS NOT |
| | ACCEPTABLE AS IT DOES NOT SATISFY THE DRINKING FOUNTAIN |
| | REQUIREMENTS. |
| | 6) SECOND REQUEST: THERE APPEARS TO HAVE BEEN AN |
| | EXISTING DRINKING FOUNTAIN (SEE PERMIT # 14050704) |
| | HOWEVER IT WAS IN A DIFFERENT LOCATION THAN WHERE IT IS |
| | NOW SHOWN. PER WPB FBC 107.2.1, PROVIDE A SANITARY AND |
| | WATER RISER DIAGRAM FOR THE DRINKING FOUNTAIN. INCLUDE |
| | CONNECTION TO EXISTING SERVICES. ALTERNATIVELY THE |
| | OWNER CAN ADD THE WATER DISPENSER IN ADDITION TO THE |
| | HIGH LOW DRINKING FOUNTAIN. |
| | 7) SHT. A-2 - ACCESSIBLE TOILETS FOR KIDS DETAILS - THE |
| | FRONT ELEVATION OF THE WATER CLOSET SHOWS THE |
| | CENTERLINE AT 12-15 INCHES AND THE WHEELCHAIR |
| | ACCESSIBLE WATER CLOOSET PLAN SHOWS 12-18 INCHES. |
| | CORRECT THE DETAIL. |
| | 8) ON A-3 DETAIL #6 PLEASE REMOVE THIS DETAIN AS IT IS |
| | NOT RELEVANT TO THIS RENOVATION TO THIS EXISTING |
| | BUILDING. |
| | 9)PROVIDE THE ELECTRIC TANKLESS WATER HEATER |
| | SPECIFICATIONS |
| | 10) ON SHEET A-1 NEXT TO THE LOCKED STORAGE ROOM THERE |
| | IS AN ITEM IDENTIFIED AS POS? PLEASE PROVIDE MORE |
| | DETAIL |
| | 11) ON SHEET MEP AND SHEET A-1 UNDER GENERAL NOTES. |
| | PLEASE PROVIDE MORE INFORMATION ON THE BATHROOM FLOORS |
| | AND WALLS TO 48" TO BE "NON-POURS AND SCRABBLE"? |
| | 12)SECOND REQUEST: PER WPB FBC 107.2.1, SUBMIT A SLAB |
| | REPAIR DETAIL FOR REVIEW AND ONCE APPROVED HAVE TWO |
| | COPIES AT THE JOB SITE. SHOW THE WIDTH OF THE REPAIR, |
| | THE MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED, |
| | AND THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH |
| | OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE |
| | EXISTING SLAB, THE ANCHORING MATERIAL FOR THE DOWELS |
| | AND THE SPACING OF THE DOWELS ON CENTER. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND |
| | THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. A |
| | COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A |
| | FINAL INSPECTION. |
| | 13) SECOND REQUEST: REFER TO PERMIT 14050704. THERE WAS |
| | A SINK ADJACENT TO THE PLUMBING WET WALL IN THE ROOM |
| | WHERE THE 7-12 YEAR OLD RESTROOMS ARE LOCATED ON SHEET |
| | MEP. PLEASE INDICATE IF THIS IS TO BE CAPPED OFF ON THE |
| | PLANS. |
| | 14) THE ACCESSIBILITY CODE SEC. 604.9 ADDRESSES |
| | SPECIFICATIONS FOR CHILDREN AGES 3-4, 5-8, AND 9-12 |
| | EACH AGE GROUP SPECIFICALLY HAS SPECIAL REQUIREMENTS |
| | FOR WATER CLOSETS AND COMPARTMENTS FOR CHILDRES USE. |
| | 15) YOUR PLANS HAVE CONTINUED TO HAVE THE SAME |
| | DEFICIENCIES. IN ORDER TO HELP ME HELP YOU PLEASE |
| | CONTACT ME AT 561-805-6695 |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |