| 2020-11-04 06:18:57 | |
| | |
| | 1. IT APPEARS THAT SOME CHANGES MAY HAVE BEEN MADE TO |
| | THE PROJECT THAT WERE NOT PERMITTED. PROVIDE AN |
| | EXISTING FLOOR PLAN. THE FLOOR LAYOUT OF THE EXISTING |
| | PLAN IN CITY RECORDS DOES NOT MATCH THE LAYOUT OF THE |
| | SUBMITTED PLAN. THE RESPONSE IN THE RESPONSE NARRATIVE |
| | OF " THE OLD PERMIT PLANS MUST BE INACCURATE" DOES NOT |
| | SOLVE THIS ISSUE. WORK THAT WAS PREVIOUSLY DONE WITHOUT |
| | PERMITS MUST BE LEGALLY PERMITTED. WPB AMEND. TO FBC |
| | SEC. 107.3..5, 105.1. |
| | 2. THE CENTERLINE OF THE WATER CLOSET SHALL BE 18 |
| | INCHES MAXIMUM, NOT MINIMUM AS NOTED ON PLANS. SEE FBC |
| | ACC 604.2. THE CENTERLINE OF THE WATER CLOSET SHALL BE |
| | 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE |
| | WALL OR PARTITION. |
| | 3)THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM |
| | MEASURED TO THE TOP OF THE SEAT. FBC ACC 604.4. PER WPB |
| | FBC 107.2.1, CORRECT DETAIL ON PLAN A-3. |
| | 4) INDICATE THE ON THE PLAN THAT THE TEMPERED WATER TO |
| | THE SINK MAX 110 DEGREES BY AN APPROVED ASSE 1070 |
| | DEVICE COMPLYING WITH FBC PL 607.1.2. |
| | 5) THE 2017 ACCESSIBILITY CODE REQUIRES AT LEAST A HIGH |
| | & LOW DRINKING FOUNTAIN INCOMPLIANCE WITH 2017 |
| | FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO FEWER |
| | THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| | AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. THE |
| | WATER DISPENSER IS NOT ACCEPTABLE AS IT DOES NOT |
| | SATISFY THE DRINKING FOUNTAIN REQUIREMENTS. |
| | 6) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2. |
| | OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT |
| | MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE |
| | MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION |
| | PATH. |
| | 7) SHT. A-1 - NOTE #8 CALLS OUT A UTILITY SINK BUT |
| | THERE IS NO UTILITY SINK SHOWN ON THE PLANS. CLARIFY. |
| | 8) SHT. A-2 - ACCESSIBLE TOILETS FOR KIDS DETAILS - THE |
| | FRONT ELEVATION OF THE WATER CLOSET SHOWS THE |
| | CENTERLINE AT 12-15 INCHES AND THE WHEELCHAIR |
| | ACCESSIBLE WATER CLOOSET PLAN SHOWS 12-18 INCHES. |
| | CORRECT THE DETAIL. |
| | 9) SHT. A-2 - THE WATER CLOSET ELEVATION DETAIL SHOWS |
| | THE GRAB BARS MEASURED TO THE CENTERLINE OF THE BAR. |
| | GRAB BARS SHALL BE MEASURE TO THE TOP OF THE GRIPPING |
| | SURFACE. FBC-ACCESS. SEC. 609.4. |
| | 10) SHT. A-3 - PLUMBING FIXTURE MOUNTING HEIGHT DETAILS |
| | - THE DETAILS REFER TO THE 2007 FBC.THE 2017 FBC IS IN |
| | EFFECT. REVISE THE NOTE. ALSO, THE FIGURE NUMBERS |
| | LISTED ON THE DETAILS ARE NO LONGER IN THE CODE. |
| | 11) THE WATER HEATER DETAIL ON THE MEP PLAN SHOWS A TOP |
| | FEED WATER HEATER BUT THE WATER HEATER SPECIFICATIONS |
| | SHOW THE WATER HEATER IS BOTTOM FED. A VACUUM RELIEF |
| | LINE IS REQUIRED ON THE COLD WATER LINE PER |
| | FBC-PLUMBING SEC.504.2. |
| | 12) THE WATER HEATER PAN SHALL COMPLY WITH FBC-PLUMBING |
| | SEC.504.7 & 504.7.1. |
| | 13) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER |
| | HEATER. |
| | 14) SUBMIT DETAILS AS TO HOW THE WATER HEATER IS BEING |
| | SUPPORTED (TYPE AND SIZE OF HANGING RODS, TYPE AND |
| | LOCATION OF CONNECTIONS TO BAR JOISTS). WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 15) ACCESS SHALL BE PROVIDED TO THE WATER HEATER IN THE |
| | CEILING PER FBC-PLUMBING SEC.502.5. A LEVEL WORKING |
| | SPACE NOT LESS THAN 30 INCHES IN LENGTH AND 30 INCHES |
| | IN WIDTH SHALL BE PROVIDED IN FRONT OF THE CONTROL SIDE |
| | TO SERVICE AN APPLIANCE. |
| | |