| Plan Review Notes For Permit 20060393 |
| Permit Number |
20060393 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-11-03 15:03:42 | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM | | | SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY | | | CERTIFIED CONTRACTORS. | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM/EQUIPMENT | | | SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS | | | BY CERTIFIED CONTRACTORS. | | | | | | 3) THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT | | | THE CONSTRUCTION PERIOD. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] |
|