| 2020-07-29 09:03:11 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20060393 |
| | ADD: 2405 MERCER AVE. |
| | CONT: BUTLER CONSTRUCTION |
| | TEL: 561-832-9700 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. JULY29TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. THE PERMIT APPLICATION STATES THE WORK |
| | TO BE ACCOMPLISHED UNDER THE SCOPE OF THIS PERMIT IS |
| | FOR THE RENOVATION OF AN EXISTING RESTROOM FOR A VALUE |
| | OF $5,000.00 DOLLARS. |
| | |
| | 2A) 2ND REQUEST. SHEET A-2 STILL MAKES REFERENCE TO THE |
| | 2014 FBC. |
| | |
| | 2B) NEW COMMENT. THIS PLAN STATES THAT THE ALTERATION |
| | LEVEL IS LEVEL II. THE CITY OF WEST PALM BEACH BUSINESS |
| | TAX (OLD OCCUPATIONAL LICENSING) SHOWS THIS SPACE BEING |
| | CARLYLE THERAPY ASSOCIATION WHICH IS A BUSINESS |
| | OCCUPANCY. A CHANGE OF OCCUPANCY IS OCCURRING. |
| | THE DESIGNER OF RECORD HAS NOT MET ALL OF THE |
| | REQUIREMENTS FOUND UNDER COMMENT 468.1 FOR EDUCATIONAL |
| | OCCUPANCIES. ALL OF THE REQUIREMENTS, THERE IS NO |
| | EXISTING BUILDING CODE FOR THIS OCCUPANCY GROUP. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) SHEET A-2 MAKE REFERENCE TO THIS FACILITY TO BE A |
| | PUBLIC CHARTER SCHOOL GRADES K-8TH GRADE. PLEASE BE |
| | AWARE OF THE 2017 FBC-EXISTING CODE SCOPING |
| | REQUIREMENTS AND EXCEPTION FOUND UNDER SECTION 101.2. |
| | EXCEPTION: FOR THE PURPOSE OF PUBLIC EDUCATION AND |
| | STATE LICENSED FACILITIES, SEE CHAPTER 4 SPECIAL |
| | OCCUPANCIES OF THE FLORIDA BUILDING CODE, BUILDING. |
| | SECTION 453 DEALS WITH STATE REQUIREMENTS FOR |
| | EDUCATIONAL FACILITIES. NOT THE LOCAL BUILDING DEPART. |
| | CONCERN UNLESS THE SCHOOL BOARD SUBMITS PLANS FOR |
| | PUBLIC SCHOOLS. |
| | 4A)(1) CHAPTER 468 FOR FLORIDA?S PUBLIC & PRIVATE |
| | SCHOOLS, COLLEGES AND UNIVERSITIES. THERE IS NO |
| | EXISTING BUILDING CODE TO GO BY UNDER SPECIAL |
| | OCCUPANCIES FOUND IN CHAPTER 4. CHAPTER 468 IN ITS |
| | ENTIRITY HAS TO SHOW COMPLIANCE. |
| | |
| | 4A)(2) SEMI-COMPLIED. THERE IS NOT ENOUGH INFORMATION |
| | ON THE PLAN TO DETERMINE CODE COMPLIANCE FOR THE |
| | REQUIRED NUMBER OF FIXTURES REQUIRED UNDER THE 2017 |
| | FBC-B TABLE 2902.1 FOR EDUCATION. THE SUBMITTED TABLE |
| | GIVES A OVERALL COUNT BUT NOT BY AGE GROUP SEE THE 2017 |
| | ACCESSIBILITY CODE 604.9 AGES 5-8 AGES 9-12 FOR WATER |
| | CLOSET CENTERLINE, TOILET SEAT HEIGHT, GRAB BAR HEIGHT |
| | AND DISPENSER HEIGHT. |
| | |
| | 4B) 2ND REQUEST ACCESS. CODE TABLE 604.9.THE 2017 FBC-B |
| | 468.3.5.1 STANDARDS. EDUCATIONAL AND ANCILLARY |
| | FACILITIES SHALL BE PROVIDE WITH TOLIETS, HAND WASHING |
| | AND DRINKING FOUNTAINS FOR ALL OCCUPANTS IN RATIOS AND |
| | ACCESSIBLE AS REQUIRED BY THE FLORIDA BUILDING CODE, |
| | FLORIDA LAWS AND FEDERAL REGULATIONS. SHEET A-1 & A2 |
| | SHOWS A SINGLE DRINKING FOUNTAIN, PLEASE SHOW A DOUBLE |
| | HIGH/ LOW, PLEASE SEE IN THE 2017 FBC-ACCESSIBILITY |
| | CODE REQUIREMENTS FOR DRINKING FOUNTAINS. SHEET A-3 |
| | SHOWS COMPLIANCE WITH : |
| | |
| | 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO |
| | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | NOT SHOWN IN COMPLIANCE. PROTRUDING OBJECTS 307.2 |
| | PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING EDGES |
| | MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE |
| | THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES |
| | HORIZONTALLY IN TO THE CIRCULATION PATH. |
| | |
| | 60.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING |
| | WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE |
| | AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 5) COMPLIED. SHEET A-3 GRAB BARS. |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |