| 2020-09-28 07:31:04 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20060389 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SEE BUILDING B SQ. FT. SUMMARY ON SHEET A-1. |
| | AFTER CARE ASSEMBLY AREA HAS AN OCCUPANT LOAD OF 72 |
| | PEOPLE. PLEASE USE THIS OCCUPANT COUNT FOR THE OUTDOOR |
| | AIR CALCULATIONS FOR THE AFTER CARE ROOM ON SHEET A-4. |
| | WE MUST PROVIDE O.A. BASED ON THE OCCUPANT LOAD OF THE |
| | SPACE. FBC M TABLE 403.3.1.1 |
| | |
| | 2) BASED ON FBC M TABLE 403.3.1.1: REQUIRED O.A. FOR |
| | THIS BUILDING IS: AFTER CARE ROOM- 605 CFM; 4 |
| | CLASSROOMS- 1007CFM. SHEET A-4- THE DRAWING SHOWS AN |
| | O.A. DUCT FOR EXISTING AHU#1 BUT THE OUTDOOR AIR |
| | CALCULATIONS DO NOT SHOW THE REQUIRED OUTDOOR AIR FOR |
| | THIS ROOM. PLEASE SHOW THIS IN THE O.A. CALCULATIONS. |
| | FBC M TABLE 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |