| 2020-08-04 17:36:49 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20060389 |
| | 8/4/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A3: REMOVE THE REFERENCES TO THE FBC 2007 |
| | SHOWN IN DETAIL 6. THE ACCESSIBLE TOILET ROOM SHALL BE |
| | DESIGNED IN ACCORDANCE WITH THE FLORIDA ACCESSIBILITY |
| | CODE- 2017 SIXTH EDITION. |
| | |
| | A) DETAIL 6 GRAB BARS: REFER TO FIGURE 604.5.2 FBC ACC |
| | AND CORRECT THE REAR WALL GRAB BAR DETAIL. |
| | |
| | B) 2ND REQUEST FOR LOCATION, MOUNTING HEIGHT AND |
| | CLEARANCE FOR THE TOILET PAPER DISPENSER- SECTION |
| | 604.7. |
| | |
| | C) REFER TO FIGURES 306.2 AND 306.3 AND CORRECT THE |
| | KNEE AND TOE CLEARANCES FOR THE LAVATORY. TOE |
| | CLEARANCES SHALL BE MINIMUM 9" IN HEIGHT, AND KNEE |
| | CLEARANCE SHALL BE 11" DEEP MINIMUM AT 9" ABOVE THE |
| | FINISHED FLOOR- SECTION 306.3.3. |
| | |
| | 2) COMMENTS #5,6,7, & 8 FROM THE 1ST REVIEW LISTED |
| | BELOW HAVE NOT BEEN ADDRESSED- PLEASE COMPLY. |
| | 5) A3: PROVIDE A WATER RISER DRAWING SHOWING PIPE |
| | SIZES, LOCATIONS OF SHUTOFF VALVES, WATER HAMMER |
| | ARRESTORS, MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB |
| | AMENDMENTS TO THE FBC. NOT PROVIDED. |
| | |
| | 6) A3: PROVIDE PLUMBING FIXTURE AND DEVICE SCHEDULES ON |
| | THE PLAN- SECTION 107.2.1 WPB & SECTION 405.9. NOT |
| | PROVIDED. |
| | |
| | 7) A3: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO |
| | THE LAVATORY- SECTION 416.5 FBC P. NOT PROVIDED. |
| | |
| | 8) A1 & A3: PROVIDE THE SCOPE OF WORK FOR THE REQUIRED |
| | WATER HEATER- SECTION 607.1 FBC P. CLARIFY IF THE |
| | APPLIANCE IS EXISTING OR TO BE REPLACED. SHOW THE |
| | LOCATION AND PROVIDE PLUMBING DETAILS IF APPLICABLE. |
| | PLEASE NOTE THAT THE DEVELOPED LENGTH OF HOT OR |
| | TEMPERED WATER PIPING, FROM THE SOURCE OF HOT WATER TO |
| | THE FIXTURES THAT REQUIRE HOT OR TEMPERED WATER, SHALL |
| | NOT EXCEED 50 FEET. |
| | THE WATER HEATER DETAIL ON A3 DOES NOT SPECIFY A MAKE |
| | AND MODEL, GALLON SIZE, OR EFFICIENCY RATING. |
| | NOTE-7 SPECIFIES A MIXING VALVE BUT INCORRECT LISTING- |
| | ASSE 1070 CONFORMANCE REQUIRED- SECTION 607.1.2 FBC P. |
| | NOTE-8 INDICATES MIXING VALVE TEMPERATURE SETTING AT |
| | 140 DEGREES. TEMPERED WATER SHALL HAVE A TEMPERATURE |
| | RANGE 0F 85 TO 110 DEGREES FAHRENHEIT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |