| 2020-07-02 11:48:41 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20060389 |
| | 7/2/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A1: REFER TO SECTION 468.3.5.1 FBC B, AND |
| | TABLE 403.3 FBC P AND PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS. PROVIDE A SCHEDULE ON THE PLAN INDICATING |
| | THE REQUIRED AND PROVIDED PLUMBING FIXTURE BASED ON THE |
| | E OCCUPANCY AND OCCUPANT LOAD OF 183. PLEASE NOTE THAT |
| | A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED- REFER |
| | TO SECTION 211.1- 2113 FBC ACC PLEASE NOTE A THOROUGH |
| | REVIEW OF THE PLANS CANNOT BE ACCOMPLISHED UNTIL THE |
| | SCHEDULE IS PROVIDED- SECTION 107.2.1 WPB. |
| | |
| | 2) A1, A2: IDENTIFY THE NEW TOILET ROOM AS EITHER MALE |
| | OR FEMALE- SECTION 403.2 FBC P. |
| | |
| | 3) A3: PROVIDE ENLARGED TOILET ROOM DRAWINGS |
| | INDICATING: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- SECTION 606.2. |
| | C) TURNING SPACE DIAMETER- SECTION 304.3. |
| | D) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION |
| | 604.6. |
| | E) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE |
| | TOILET PAPER DISPENSER- SECTION 604.7. |
| | |
| | 4) A3: THE SINK FIXTURE DRAIN MUST CONNECT TO THE 3" |
| | BUILDING DRAIN DOWNSTREAM OF THE WC AND LAVATORY PER |
| | SECTIONS 912.1 AND 912.2.1 FBC P. |
| | |
| | 5) A3: PROVIDE A WATER RISER DRAWING SHOWING PIPE |
| | SIZES, LOCATIONS OF SHUTOFF VALVES, WATER HAMMER |
| | ARRESTORS, MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB |
| | AMENDMENTS TO THE FBC. |
| | |
| | 6) A3: PROVIDE PLUMBING FIXTURE AND DEVICE SCHEDULES ON |
| | THE PLAN- SECTION 107.2.1 WPB & SECTION 405.9 FBC P. |
| | |
| | 7) A3: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO |
| | THE LAVATORY- SECTION 416.5 FBC P. |
| | |
| | 8) A1 & A3: PROVIDE THE SCOPE OF WORK FOR THE REQUIRED |
| | WATER HEATER- SECTION 607.1 FBC P. CLARIFY IF THE |
| | APPLIANCE IS EXISTING OR TO BE REPLACED. SHOW THE |
| | LOCATION AND PROVIDE PLUMBING DETAILS IF APPLICABLE. |
| | PLEASE NOTE THAT THE DEVELOPED LENGTH OF HOT OR |
| | TEMPERED WATER PIPING, FROM THE SOURCE OF HOT WATER TO |
| | THE FIXTURES THAT REQUIRE HOT OR TEMPERED WATER, SHALL |
| | NOT EXCEED 50 FEET. |
| | |
| | 9) A1 & A3: CONCERNING THE REQUIRED DRINKING FOUNTAINS |
| | PLEASE SEE SECTION 211.1.2 FBC ACC- NO FEWER THAN TWO |
| | DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH SECTIONS 602.1 - 602.6, AND |
| | ONE SHALL COMPLY WITH 602.7. SECTION 602.7 REQUIRES |
| | THAT SPOUT OUTLETS FOR STANDING PERSONS SHALL BE 38 |
| | INCHES MINIMUM AND 43 INCHES MAXIMUM FROM THE FINISHED |
| | FLOOR. SHOW THE LOCATIONS OF THE FOUNTAIN AND SHOW: |
| | A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR |
| | FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC. |
| | B) KNEE AND TOE CLEARANCES- SECTION 306. |
| | C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND |
| | 602.5. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |